MXA MXP MGP Rev4 - Operating Instructions

Page 11 / 64

connect the power supply cord through a conduit.

For use in swimming pools (not when persons are in 

the pool), garden ponds and similar places, a residual 

current device with IΔN not exceeding 30 mA must be 

installed in the supply circuit.

Install a device for disconnection from the mains 

(switch) with a contact separation of at least 3 mm in 

all poles.

With a three-phase motor install an overload protection 

device with curve D appropriate for the rated current 

of the pump.

Single-phase, are supplied with a capacitor connected 

to the terminals and (for 220-240 V - 50 Hz) with an 

incorporated thermal protector.

  ATTENTION:  When  the  pump  is  fed  by  a 

frequency  converter,  the  minimum  frequency 

should not fall below 25Hz and in any case the 

total head of the pump should never be lower 

than 3 m.

7.  STARTUP AND OPERATION
7.1.  Preliminary checks before start-up of the 

pump

Do not start-up the device in case of damaged parts.

7.2. First starting

OFF

 

  

  

ATTENTION: never run the pump dry. Start the 

pump after filling it completely with liquid.

When the pump is located above the water level 

(suction lift operation par. 13 fig. 2) or with a positive 

suction head which is too low (less than 1 m) to open 

the non-return valve, fill the pump through the priming 

hole (par. 13 fig. 4).

When the liquid level on the suction side is above 

the pump (inflow under positive  suction head par. 13 

fig. 1), fill the pump by opening the suction gate valve 

slowly and completely, keeping the delivery gate valve 

open to release the air.

Before starting, check that the shaft turns by hand. For 

this  purpose  use  the  screwdriver  notch  on  the  shaft 

end on the ventilation side.

When starting, with a three-phase motor, check 

that the direction of rotation  is  as  shown  by  the 

arrows on the lantern bracket. 

Otherwise, disconnect electrical power and reverse 

the connections of two phases.

Check that the pump works within its 

field  of  perfor-mance  and  that  the  absorbed  current 

shown on the name-plate is not exceeded. Otherwise 

adjust  the  delivery  gate  valve  or  the  setting  of  any 

pressure switches.

If a priming loss occurs (interruption of delivery flow) 

or if a pressure oscillation is indicated by the pressure 

gauge,  make  sure  all  the  suction  pipe  couplings  are 

perfectly sealed and tighten the two sealed plugs on 

the pump casing. 

  Never  run  the  pump  for  more  than  five 

minutes with a closed gate valve.

Prolonged operation without a change

of water in the pump causes dangerous increases of 

temperature and pressure.

When the water is overheated due to prolonged 

operation  with  a  closed  port,  stop  the  pump  before 

opening the gate valve. 

To avoid any risk of danger to users and the creation of 

harmful thermal stress in the pump and system due to 

large temperature differentials, wait until the water has 

cooled inside the pump before starting again.

If  the  water  is  overheated  on  account  of  prolonged 

operation  with  a  non-primed  or  insufficiently  filled 

pump  (suction  lift  operation),  wait  until  cool  before 

opening the draining and filling plugs.

  Care must be taken when the pumped fluid 

has a high temperature. Do  not  touch  the  

fluid when its temperature is higher than  60 

°C. Do not touch the pump when the surface 

temperature is higher than 80 °C.

7.3. Automatic regulator IDROMAT

       (can be supplied on request)

For automatic control of starting/stopping of the pump 

when utilization points are opened/closed.

For protection of the pump:

•against dry running;

•against the risk of operation without water at the inlet 

(caused by a lack of water inflow in the inlet pipe under 

positive  suction  head,  by  a  non-immersed  suction 

pipe,  by  excessive  suction  lift  or  by  air  entering  the 

suction pipe);

•against operation with closed connection ports.

See installation examples par. 13 fig. 1, fig. 2.

7.4. Self-priming (Only for MXA)

(Capability  to  clear  the  air  in  the  suction  pipe  when 

starting with the pump located above the water 

level).

Conditions for self-priming:

•  suction  pipe  with  connections  perfectly  airtight  and 

properly immersed in the water to be lifted;

•  discharge pipe with a straight vertical free line above 

discharge port, before a non-return valve par. 13 fig. 

1.

•  pump    casing  completely  filled  with  clean  cold 

water  berfore starting. 

The  pump  is  not self-priming with liquids containing 

oil, alcohol or foaming substances.

The  check  valve  (par.  13  fig.  1)  prevents  reverse 

siphoning through the pump when the pump is stopped 

and retains water in the pump for the next start.

Without a foot valve or a check valve on the suction 

connection the filling operation must be repeated 

before each start-up.

  ATTENTION: avoid a prolonged operation 

with  unprimed  pump, without  water 

delivery from the completely opened outlet.

If the pump does not prime in 5 minutes: 

stop the motor, remove the priming plug 

and add more water.

If  necessary,  repeat  the  priming  operation  after  the 

pump has been first emptied and then completely filled 

with clean cold water.

7.5. Switch off of the pump

ON

  

  

  The  appliance  must  be  switch  off  every  time 

there are faults. (see troubleshooting).

The  product  is  designed  for  a  continuous  duty,    the 

switch  off  is  performed  by  disconnecting  the  power 

supply by means the expected disconnecting devices. 

(see paragraph “6.5 Electrical connection”).

8.  MAINTENANCE

Before any operations it's necessary to disconnect the 

power supply. 

If  required  ask  to  an  electrician  or  to  an  expert 

technician.

MXA MXP MGP Rev4.indd   11

13/07/17   17:03

Summary of Contents for MGP

Page 1: ... κλειστού τύπου αντλίες åÓÌÓ ÎÓ Ì Â Ó ËÁÓÌÚ Î Ì Â ÏÌÓ ÓÒÚÛÔÂÌ Ú Â Ì ÒÓÒ 卧式多级直联泵 MXP MGP MXA ISTRUZIONI ORIGINALI PER L USO Pagina 2 Italiano OPERATING INSTRUCTIONS Page 8 English BETRIEBSANLEITUNG Seite 14 Deutsch INSTRUCTIONS POUR L UTILISATION Page 20 Français INSTRUCCIONES DE USO Página 26 Español DRIFT INSTALLATIONSANVISNINGAR Sidan 32 Svenska BEDIENINGSVOORSCHRIFT Pagina 38 Nederlands ΟΔΗΓΙΕΣ...

Page 2: ...s a risk that the machine could damage or compromise personnel safety The failure to observe electrical information and warnings could damage the machine or compromise personnel safety i Notes and warnings for the correct management of the machine and its parts Operations that could be performed by the final user After carefully reading of the instructions is responsible for maintenance under norm...

Page 3: ...taly MONTORSO XXXXXXX Q min max X X m3 h XXXXXXX H max min X X m IP XX n XXXX min 220 380Y V3 50Hz cosø X X X A XXXXXXXX S1 l cl X X kg X kW XHp S F VICENZA 1 2 3 4 5 6 7 8 9 10 16 15 14 13 12 11 3 TECHNICAL FEATURES 3 1 Technical data Dimensions and weight see technical catalogue Nominal speed 2900 3450 rpm Protection IP54 Supply voltage Frequency up to 240V 1 50 60 Hz up to 480V 3 50 60 Hz Check...

Page 4: ...ps so that they do not transmit stress strain or vibrations to the pump par 13 fig 3 Tighten the pipes or union coupling to the extent sufficient to ensure a tight seal par 13 fig 6 Excessive torque may cause damage to the pump When the pipe or union coupling is mounted keep the pump casing connection blocked with a second wrench making sure the connection is not deformed by excessive tightening T...

Page 5: ...ump before opening the gate valve To avoid any risk of danger to users and the creation of harmful thermal stress in the pump and system due to large temperature differentials wait until the water has cooled inside the pump before starting again If the water is overheated on account of prolonged operation with a non primed or insufficiently filled pump suction lift operation wait until cool before...

Page 6: ...e is a risk of freezing par 13 fig 5 Before restarting the unit check that the shaft is not jammed and fill the pump casing completely with liquid 8 2 Dismantling the system Close the suction and delivery gate valves and drain the pump casing before dismantling the pump 8 3 Dismantling the pump OFF Close the suction and delivery gate valves and drain the pump casing before dismantling the pump par...

Page 7: ...See point 2a also 4 Insufficient flow 4a Pipes and accessories with diameter too small causing excessive loss of head 4b Presence of deposits or solid bodies in the internal passages of the rotor 4c Rotor deteriorated 4d Worn rotor and pump case 4e Excessive viscosity of the liquid pumped if other than water 4f Incorrect direction of rotation 4g Suction head excessive in relation to the suction ca...

Page 8: ... 标准维护工作 必须由有资格的专业电工才能进行的操作 专业电工 有资格的专业电工 负责所有电气 设备的运行包括维护 应具有高压电资格 必须由有专业技术资格的人才能进行的操作 专业技术人员 正常状态下 具有产品安装和 维护能力的专业技术人员 可以从事电气和机 械方面的维护工作 能够从事简单的与设备维 护相关的电气和机械方面的操作 指示必须使用个别的保护装置 OFF 必须关断电源并断开与电源的连接才能进行的 操作 ON 必须接通电源才能进行的操作 1 2 制造商名称和地址 制造商名称 CALPEDA S P A 地址 Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 授权操作者 本产品只能由有经验的终端用户和专业技术人员操作 i 禁止终端用户操作那些只能由专业技术人员操 作的工作 ...

Page 9: ...专业技术人员必须认真遵从所有的适 用标准和法律 包括产品应用地当地的规章 产品安装使用应符合现行的安全法规 不当的使用可能会对人身 动物和其他对象造成损害 制造商对由于不当使用或未按本操作手册和标牌的标 示使用所造成的损坏不负责任 i 按照日程维护计划表操作并及时更换损坏的部 件可使产品工作在最佳状态 使用CALPEDA S P A或其指定代理商提供的原 厂配件 不要撕下或改变产品上的标识 当产品有问题或部件有损坏的情况下不要启动 产品 由于维修时会全部或部分的拆开产品 因此之前 务必断开供电电源 4 2 安全装置 本产品具有全外部壳体 可防止与内部部件的任何接触 4 3 剩余风险 当按照本产品的设计功能和所有安全规则使用本产品 时没有剩余风险 4 4 通告和安全预示 没有任何安全预示在此类产品上面 4 5 个别的保护装置 在安装 使用和维修期间 建议操作人员使用适合此 操作的个别保护装置...

Page 10: ...7 2 首次启动 OFF 请注意 千万不要使泵干态运行 一定先注水后再启动泵 当泵位置高于水面 吸上扬程为负章13 图3 时 或者正压 头太小 小于1m 不足以打开止回阀 应通过自吸孔注水 章13 图 4 当泵位置低于水面 吸上水头为正 章13 图 1 慢慢打 开吸入端闸阀 直到完全打开 以此对泵注水 这时 应确保出水端的闸阀处于打开状态以排除空气 启动前 应手工检查轴的自由度 方法是 在电机侧用螺丝刀旋转轴端即可 对于三相电机 要检查旋转方向是否如泵盖上的箭头 方向所示 否则 切断电源 并改变其中两相的联接 确认泵工作在其性能参数范围内 实际的工作电流不 能超过铭牌上标注的电流值 否则应调整出口阀门开 度或压力开关的设置 如果吸不上水 不出水 或者压力表显示压力波动 应检查并确保所有的入口管路连接气密性完好并保证 泵壳上的加 排水堵密封完好 永远不要让泵闭阀运行超过5分钟 泵中的水长期的...

Page 11: ...体 章13 图 5 在再次启动泵 电机机组前 一定检查轴是否被卡住 并往泵内注水 8 2 系统的分解 分解前 关闭进出口隔栅 8 3 泵的拆解 OFF 关闭进出口闸阀 拆卸水泵前排空水泵 图5 拆卸及回装详见构造图中的剖面图 9 处理 OFF 产品的最终处理应由专业公司操作 确保专业公司是按照材料分类方式处理 按照当地的法规和有关环境保护的国际准则处理 10 备件 10 1 订购备件 订购备件时请根据剖面图提供备件的名称和位置编号 及泵铭牌上的数据 型号 参数和序列号 备件需求请电话 传真 邮件给CALPEDA S P A 11 部件名称 名称 14 00 泵壳 14 04 带垫片的注水堵 14 06 O形圈 14 12 带垫片的放水堵 14 16 O形圈 14 20 O型圈 14 24 螺丝 16 00 入口壳体 16 14 柱塞阀 15 15 弹簧 16 16 O型圈 16 17 单流...

Page 12: ...到位并正确连接 3b 清洁或更换底阀并使用适合于工况的进口管路 3c 清洁过滤器 或更换 同时参见2a 4 流量不足 4a 管路及其附件直径过小导致水 头损失过大 4b 流道内有沉积物或固体异物 4c 转子腐蚀损坏 4d 转子和泵壳磨损 4e 泵送介质粘度过高 不同于 水 4f 旋转方向错误 4g 吸程超过了泵的自吸能力 4h 入口管路过长 4a 请使用符合工况的管路及其附件 4b 清洁转子并安装入口过滤器以防止外部固体异物进入 4c 更换转子 如果需要请联系授权服务中心 4d 更换转子和泵壳 4e 泵不适用 4f 在控制柜内或电机接线盒内对调任意两根接线 4g 请尝试部分关闭供水阀门和 或降低泵的安装高度 液 体将被吸入 4h 使泵尽量靠近入口水箱以便缩短进口管路 如有必要应 选用大口径进水管 5 泵 的 噪 音 和 震动 5a 转子不平衡 5b 轴承磨损 5c 泵和管路未固定到位 5d...

Page 13: ...ico Draining Entleerung Vidange Vaciado Avtappning Aftappen Αποστράγγιση ëÎË 排空 Fig 2 Funzionamento in aspirazione Suction lift operation Saugbetrieb Fonctionnement en aspiration Funcionamiento en aspiración Sugande funktion Zuigsituatie Θέση λειτουργίας με κάθετη αναρρόφηση ê ÓÚ Â Û Ó Ìfl ÊË ÍÓÒÚË 负吸水头工作 Regolatore automatico Automatic regulator Schaltautomat Regulateur automatique Regulador autom...

Page 14: ...N 25 Øi 28 mm G 1 1 4 DN 32 Øi 36 mm MXA 205 405 Hs Hs MXA 205 203 2 0 4 404 4 0 5 403 404 204 100 200 450 600 203 100 200 450 600 Hs m 2 4 6 8 405 100 450 600 600 500 500 600 600 h mm 205 500 500 500 600 403 100 450 600 600 1 2 3 4 5 6 7 8 m 20 10 25 15 5 ft t min 0 5 1 2 3 4 Valvola di non ritorno Check valve Rückschlagventil Clapet de non retour Válvula de retención Backventil Terugslagklep Βαλ...

Page 15: ...3 25 01 28 00 25 10 64 15 25 11 25 11 25 11 25 10 64 15 28 08 MXP 403 MXP 403 60 MXP 202 MXP 402 MXP 202 60 MXP 402 60 MXP 201 60 MXP 401 60 MXP 203 60 MXP 402 60 64 15 25 10 MXP 403 60 2 MXP 205 MXP 405 MGP 205 MGP 405 3 MXP 405 MGP 405 MXP 404 MXP 201 60 MXP 202 60 MXP 401 60 82 04 14 04 MGP 404 MGP 405 MGP 403 MGP 203 14 00 14 12 MGP 402 MGP 202 14 24 70 00 Tab 1 TAB 1IEC 60335 1 Corrente nomin...

Page 16: ...M MXP MXPM MGP MGPM pomptype en serienummer zoals vermeld op de typeplaat aan de EG voorschriften 2006 42 EU 2009 125 EU 2014 30 EU 2014 35 EU voldoen Verordening van de commissie nr 640 2009 SF VAKUUTUS Me CALPEDA S p A vakuutamme että pumppumme MXA MXAM MXP MXPM MGP MGPM malli ja valmistusnumero tyyppikilvcstä ovat valmistettu 2006 42 EU 2009 125 EU 2014 30 EU 2014 35 EU direktiivien mukaisesti ...

Reviews: