Calix ODC-80 Installation Guide
35
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Procedure to install or replace a rectifier module
Step
Action
1.
Unbolt and remove the cover plate (or module to be replaced).
2.
Set the rectifier module AC switch to OFF.
3.
Slide the new module into the slot and tighten the front
bolts to secure the module in place.
4.
On the Alarm Control Unit, set the matching RFA DIS switch
to the right for each rectifier module installed to enable alarm
monitoring for the rectifier modules.
For any slot not containing a rectifier module, set the matching RFA DIS
switch to the left for OFF.
The illustration shows the switches set to factory defaults of ON for module
positions 1, 2, and 3, and set to OFF for position 4.
5.
Set the rectifier module AC switch to ON.
Summary of Contents for ODC-80
Page 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11 ...
Page 2: ......
Page 6: ......
Page 7: ...1 Chapter Before You Begin Installing the ODC 80 ...
Page 8: ......
Page 23: ...2 Chapter Placing the ODC 80 on a Pad ...
Page 24: ......
Page 30: ......
Page 31: ...3 Chapter Installing Power Subscriber Cables and Equipment ...
Page 32: ......
Page 74: ......
Page 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80 ...
Page 76: ......
Page 80: ......
Page 92: ......
Page 103: ...5 Chapter Reference ...
Page 104: ......
Page 106: ......