Low battery alarm
Alarm output
When the alarm occurs, the following message displays:
TID-000 01-09-10 13-15-00
* 001 REPT ALM ENV
"N2-1:MN,BATTERY,NSA,9-10,13-15-00,NEND;"
Clearing output
You will see this message once the alarm has been cleared from the system.
TID-000 01-09-10 13-15-00
A 001 REPT EVT ENV
"N2-1:BATTERY,CL,9-10,13-15-00;"
Description
Severity
The low battery (BATTERY) alarm indicates that the battery voltage in
the outdoor cabinet has dropped below -46 VDC.
Once the low battery alarm has been initiated the system has a limited
amount of time before the low voltage disconnect for the outdoor cabinet
will engage. Reestablish commercial power to the cabinet or connect a
backup generator to prevent a service disruption.
Major