Calix ODC-80 Installation Guide
83
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Low voltage disconnect alarm
Alarm output
When the alarm occurs, the following message displays:
TID-000 01-09-10 14-15-00
** 001 REPT ALM ENV
"N2-1:MJ,LVD,NSA,9-10,14-15-00,NEND;"
Clearing output
You will see this message once the alarm has been cleared from the system.
TID-000 01-09-10 14-15-00
A 001 REPT EVT ENV
"N2-1:LVD,CL,9-10,14-15-00;"
Description
Severity
The low voltage disconnect (LVD) alarm indicates that the outdoor
cabinet battery voltage has reached -42 VDC and the cabinet will be
shut down soon.
The low voltage disconnect will be activated when the battery voltage
in the cabinet reaches -44 VDC. Once the low voltage disconnect has
been activated the Calix C7 equipment will shut down and customer
will be out of service.
Major