background image

 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 267

EPC series circuit breaker enclosure with 

interlocked Arktite

®

 receptacle

Installation & maintenance information

APPLICATION 

EPC Series circuit breakers with interlocked Arktite recepta cle are designed 

for use as a service outlet to portable electric equipment with the circuit 

breaker providing overcurrent and short circuit protection.
EPC Series circuit breakers are rated at 20, 30, 40, 50, 70, 90 and 100 

amperes. The Arktite receptacles are rated at 30, 60 and 100 amperes, 

and provided in 2-wire, 3-pole and 3-wire, 4-pole designs. The receptacles 

provide attachment of the grounding wire to an extra grounding pole and 

direct connection between plug and receptacle housings and grounding 

pole. The polarized receptacle is compatible with APJ, NPJ and CPH Series 

Style 2 plugs with the same style, current rating and number of poles. EPC 

Series circuit breakers with interlocked Arktite receptacle are designed for 

use in Class I, Groups C, D; Class II, Groups F, G; and Class Ill hazardous 

(classified) areas as defined by the National Electrical Code® (NEC) as well 

as in damp, wet, or corrosive locations.

CAUTION

To reduce the risk of ignition of hazardous atmospheres, do not use in 

Class II, Group F locations that contain electrically conductive dusts.

!

The interlocked receptacle and mating plug cannot be made or broken 

under load. 
The circuit breaker cannot be closed until the plug is fully inserted into the 

receptacle. When the plug is fully inserted and the circuit breaker closed, 

the plug cannot be removed until the breaker is opened. 

ENCLOSURE INSTALLATION 

1.  Install conduit sealing fittings into EPC enclosure hubs before fastening 

unit to mounting location for installation of conduit and power supply 

wires. 

2.  Select mounting location that will provide suitable strength and rigidity 

for supporting the unit and all contained wiring. Be sure to provide 

adequate space for insertion and removal of the plug.

3.  Fasten unit to mounting location: Position top keyway slot onto 5/16 

inch diameter bolt or lag screw; level unit; then secure bottom at 

two open slots with 5/16 inch diameter bolts or lag screws. Refer to 

DIMENSIONS section of these instructions.

4.  Depress locking tab and remove top cover using a standard pinch bar 

or similar tool as a pry between the notches on the rim of the cover 

and the lug attached to the center section of the enclosure.

5.  Install circuit breaker into units supplied without one.

•  Select the proper circuit breaker from Table I.
•  Secure circuit breaker to mounting plate in location indicated on 

mounting plate label.

•  Secure upper operating rod guide with two upper circuit breaker 

mounting screws.

•  Adjust operating rod bracket as necessary to captivate circuit 

breaker toggles. 

6.  Install wiring. Refer to WIRING CONNECTION section of these 

instructions.

7.  Check wiring per ELECTRICAL TESTING section of these instructions.
8.  Replace top cover.

WARNING

To prevent ignition of hazardous atmospheres

, disconnect the device 

from the supply circuit before opening. Keep tightly closed when in 

operation. Conduit runs must have a sealing fitting connected within 18 

inches of the enclosure.
Electrical power must be off before and during installation and 

maintenance. 

!

CAUTION

• 

Hazardous location information specifying class and group listing of 

each device is marked on the nameplate of each enclosure.

• 

No conduit openings are to be added in the field.

• 

All unused conduit openings must be plugged. Plug must engage a 

minimum of five full threads and be a minimum of 1/8 inch thick.

• 

All conduits entering and leaving the enclosure, must be sealed 

with explosionproof seals within 18 inches of the enclosure. 

• 

Conduit sealing fittings must be installed in each attached conduit 

run to comply with the latest edition of the NEC Section 501-5 and/

or 502-5 plus any other applicable code.

!

30, 60 and 
100 ampere 
size EPC

®National Electrical Code is a Registered Trademark of the National Fire Protection Association.

IF 267 • 04/20                                                         Copyright © 2020, Eaton’s Crouse-Hinds Division                                                                   Page 1

CAUTION

• 

Check for dirt, grit or other foreign material on the threads. If any 

such material settles on these threads, clear them with kerosene or 

Stoddard solvent*, then lubricate with Crouse-Hinds Company Type 

STL thread lubricant. 

*To avoid the possibilities of an explosion, oxidation and corrosion, do 

not use gasoline or similar solvents. 

!

Summary of Contents for EPC Series

Page 1: ...ttom at two open slots with 5 16 inch diameter bolts or lag screws Refer to DIMENSIONS section of these instructions 4 Depress locking tab and remove top cover using a standard pinch bar or similar tool as a pry between the notches on the rim of the cover and the lug attached to the center section of the enclosure 5 Install circuit breaker into units supplied without one Select the proper circuit ...

Page 2: ... have interchangeable attachment plugs as stated in paragraph 210 7F of the National Electrical Code Circuit breaker Enclosure Receptacle with spring door housing Rating Hub size Circuit breaker amperage Cat Without circuit breaker With circuit breaker Cat Cutler Hammer EHD Cat General Electric TED 30A 2 wire 3 pole Style 2 2 pole 480 VACA or 250 VDC 600 VACB 11 4 20 EPC43032 EPC43032 WT20 2 EPC43...

Page 3: ...E EPC enclosures identified with the addition of Suffix S4 to catalog number are supplied with receptacle contacts rotated 22 1 2 degrees for special polarity applications They are compatible only with plugs built with the same special feature APJ NPJ Dimensions h and hh are exposed portion of plug when engaged with receptacle Receptacle Breaker a b c d e f g h hh k l 30A 20 50A 24 105 8 143 8 93 ...

Page 4: ...m complete all wiring connec tions and replace upper cover INTERLOCK TEST With the Arktite plug removed from the receptacle it should be impossible to move operating handle to on position Insert plug into receptacle This should actuate the interlocking mechanism and allow the operating handle to be moved to ON position The plug at this time should resist all normal efforts to withdraw it from the ...

Reviews: