background image

45

Sequence of Operation / Settings

• 

Master / Slave switch: 

Master

• 

Pump Exercise: 

OFF

• 

Priority: 

ON

• 

AUX During Priority Demand: 

OFF

• 

System Pump Status During Zone 1 Demand 

Jumper: 

OFF

• 

Sec Pump Status During Zone 1 Demand 

Jumper: 

OFF

• 

A demand occurs from a thermostat on zones 

2-6  closing  R  to  W.    The  “T-STAT  CALL”  LED 

illuminates for the corresponding zone.

• 

ZVR control sends 24 VAC to the corresponding 

zone MOTOR terminals to open the zone valve.

• 

When the zone valve end switch closes, 

the  “VALVE  OPEN”  LED  illuminates  for  the 

corresponding zone.  ZVR control sends 120 

VAC to SYSTEM PUMP output.  The control will 

close the XX contacts to signal the boiler of a 

demand and close the AUX contacts to signal the 

ECM pump to start.

• 

When the thermostat demand is satisfied R to 

W will open and the “T-STAT CALL” and “VALVE 

OPEN” LEDs will turn off.  24 VAC is dropped to 

the corresponding zone MOTOR terminals.

• 

If no other zones are calling for heat the XX 

contacts will open terminating the demand for 

heat to the boiler.  The AUX contacts will also 

open terminating the demand to the ECM pump.  

The 120 VAC is dropped to the SYSTEM PUMP.

• 

If a demand occurs from the DHW aquastat 

(T-STAT 1), the “T-STAT CALL” and the “VALVE 

OPEN” LEDs illuminate for zone 1.  (When using a 

pump for zone 1 instead of a zone valve a jumper 

must be installed on the ZONE 1 END SWITCH 

terminals.)

• 

If any other zone was calling for heat (zones 

2-6) when zone 1 is calling 24 VAC is dropped 

to those zone’s MOTOR terminals.  The “T-STAT 

CALL” and “VALVE OPEN” LED will also turn off.  

The AUX contacts will also open terminating the 

demand to the ECM pump.

• 

The XX and the ZONE 1 E/S contacts close to 

signal a DHW demand to the boiler.

• 

The ZONE 1 PUMP output delivers 120 VAC.

• 

120 VAC is dropped to the SYSTEM PUMP.

• 

Once the DHW aquastat (T-STAT 1) is satisfied it 

will open R to W and 120 VAC to ZONE 1 PUMP 

is dropped.  The ZONE 1 E/S and XX contacts 

open.

• 

If a call for heat exists from zones 2-6 the 

corresponding “T-STAT CALL” LED will illuminate 

again and 24 VAC will be delivered to their zone 

MOTOR terminals.  

• 

When the zone valve end switch closes, 

the  “VALVE  OPEN”  LED  illuminates  for  the 

corresponding zone.  ZVR control sends 120 

VAC to SYSTEM PUMP output.  The control will 

close the XX contacts to signal the boiler of a 

demand and close the AUX contacts to signal the 

ECM pump to start. 

• 

When all the thermostat demands are satisfied 

R  to  W  will  open  and  the  “T-STAT  CALL”  and 

“VALVE  OPEN”  LEDs  will  turn  off.    The  XX 

contacts will open terminating the demand for 

heat to the boiler.  The AUX contacts will also 

open terminating the demand to the ECM pump.  

The 120 VAC is dropped to the SYSTEM PUMP.

DHW Time Out \ Freeze Prevention Feature

• 

After one hour of a priority demand, the 

control will open the ZONE 1 E/S contacts and 

drop power to ZONE #1 PUMP and ZONE 1 

MOTOR terminals.

• 

If a call for heat exists from zones 2-6, the 

control will satisfy those demands before 

going back to the priority demand.

• 

After zones 2-6 have been satisfied, the 

control will go back to the priority demand and 

reset the one hour timer.

Description of terminals

 

= Ground

= Neutral (Common leg of 120 VAC)

= Line (Hot leg of 120 VAC)

Thermostat terminals

R         = 24 VAC
W        = Heat call
C        = Common of 24 VAC

Boiler terminals

XX

 = Dry contact rated up to 120 VAC, 2 Amps, 

which is typically connected to TT on boiler control, 
closes when any zone calls including priority. 

ZONE 1 E/S 

= Dry contact rated up to 120 VAC, 

2 Amps, will close with any call to ZONE 1.  Zone 
1 can be enabled as a priority zone, typically used 
for heating domestic hot water.  The ZONE 1 E/S 
can be used to close a DHW contact on boiler 
controls equipped with these features. 

AUX 

= Dry contact, rated up to 120 VAC, 2 Amps, 

close when any zone calls and can be used 

as 

signal to a variable speed self regulated pump or 
other controls.

Pump terminals

SYSTEM PUMP

 = Runs when any zone calls for 

heat.

SEC PUMP

 = Runs when any zone calls for heat. 

ZONE 1 PUMP

 = Runs when zone 1 thermostat 

calls for heat and zone 1 end switch has closed.  
A jumper is required between the ZONE 1 END 
SWITCH terminals when using a pump for ZONE 
1 instead of a zone valve.

STATUS DURING ZONE 1 DEMAND ON / OFF: 

When status jumper is placed on ON pins, the 
secondary and / or system pump will continue to 
operate during Zone 1 demand. When jumper is 
placed on OFF pins, the corresponding pump will 
be OFF during Zone 1 demand.

Valve terminals

Motor = 24 VAC to power the zone valve motor
End Switch = Connects to end switch on zone 
valve. Must be jumped if using a  2–wire zone valve. 

WARNING: 

NEVER CONNECT R & C DIRECTLY, 

this will be a direct short on the 24 VAC supply

Summary of Contents for Z-one ZSR103

Page 1: ...DHW capable of switching line voltage t High capacity transformer t Large terminal connections t Simpli ed wiring with extra ground terminals t Heavy duty sealed relays t All pumps fuse protected with...

Page 2: ...ctrical codes WARNING Avoid electrical noise interference Do not install near large conductors electrical machinery or welding equipment Avoid locations where excessive moisture corrosive fumes vibrat...

Page 3: ...is damaged replace control with functional one Mounting Mount the Caleffi Z one switching relay box to a suitable surface Slotted holes are provided for mounting purposes Do not mount to a surface th...

Page 4: ...edbypositioning five dip switches for the following operations Master Slave allows for unlimited expansion to additional ZSR or ZVR relays boards Priority ON OFF When priority switch is ON upon demand...

Page 5: ...es wiring easy Three extra ground screw terminals connection allows fast grounding of pumps eliminating the need for extra wire connectors Pump terminals have 120 VAC outputs for simpli ed pump connec...

Page 6: ...ZONE2 ZONE3 ZONE4 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM AUX 4 Zone ZSR104 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON...

Page 7: ...MP 3 N TRANSFORMER L N L PUMP 4 N L PUMP 5 N L PUMP 6 N POWER ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4...

Page 8: ...T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120...

Page 9: ...1 1...

Page 10: ...ump can be operated Zone priority is selectable with 1 hour time out feature Other features include pump exercising selectable post purge and 3 pump ground terminals for simpli ed wiring The ZVR Serie...

Page 11: ...zone valve control Product overview 26 Circuit board 27 Cover removal Transformer Installation 28 Product details 29 C1 Mod Con boiler hydro separator zone valves 30 C2 Mod Con boiler indirect DHW on...

Page 12: ...MP 4 N L PUMP 5 N L PUMP 6 N THM 5 C R W T T COM THM 6 C R W T T COM PWR ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 DipSwitches Master Slave Priority OFF Priority ON Primary OFF Primary ON Exercise OFF Exerc...

Page 13: ...g a Taco 570 valve to Caleffi Z one Relay When connecting the Taco 570 zone valve to the Caleffi Z one Relay the wiring of this valve can only be done in one way The left motor terminal on the ZVR ser...

Page 14: ...0 VAC pump with boiler enable or two devices without boiler enable 5 A capacity each relay 10 A total Rear knock outs for mounting onto 4 x4 junction box High capacity 6VA transformer Simplified wirin...

Page 15: ...p connection Dual labeled T stat terminals Compatible with 2 3 and 4 wire T stats Replaceable fuses 6 VA Transformer Keyhole mounting which fits a 4X4 junction box Pre installed jumper Rear knockout f...

Page 16: ...om power zone transformer N L L RELAY 1 C N O N C C N O N C RELAY 2 Calef single zone relay L N A1 Single thermostat Hydronic diagram is for illustration purposes only some components have been remove...

Page 17: ...the thermostat demand is satisfied R to W will open and the ZONE LED will turn off The control will remove power from relays 1 and 2 opening C to NO This will drop 120 VAC to your pump and terminate t...

Page 18: ...N C C N O N C RELAY 2 Calef single zone relay 4 wire zone valve 4 wire zone valve 4 wire zone valve R W 24 VAC T T R W R W End switch wires L N A2 Multiple thermostats Hydronic diagram is for illustr...

Page 19: ...factory installed jumper between L and C When all the thermostat demands are satisfied the zone valves will close and the end switch will open R to W The ZONE LED will turn off The control will remove...

Page 20: ...TRV TRV TRV R W C T T com power zone transformer N L L RELAY 1 C N ON C C N ON C RELAY 2 ZSR101 T T L N A3 Single master thermostat panel radiators with TRVs variable speed pump Hydronic diagram is fo...

Page 21: ...red room temperatures The room temperatures will then be controlled by each individual thermostatic radiator valve by adjusting the flow through the radiator making this a fitting application for a va...

Page 22: ...re Selectable post purge and exercise Dry contacts X X AUX ZONE 1 E S capable of switching line voltage High capacity transformer Large terminal connections Simplified wiring with extra ground termina...

Page 23: ...labeled T stat terminals Compatible with 2 3 and 4 wire T stats Selectable DIP switches LED for each zone 120 VAC zone pump outputs 120 VAC input power connection ZONE1 ES closes only during a demand...

Page 24: ...release from base Roll cover off base Mounting Do not mount to a surface that exceeds 115 F 45 C The unit must be only located in dry interior locations Use only copper conductor supply wire suitable...

Page 25: ...l PRIORITY PUMP Runs when zone 1 calls Can be programmed to be the priority zone L Line hot leg of 120 VAC to power the pump N Neutral leg of 120 VAC to power the pump Remote Enable allows for input o...

Page 26: ...MMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE...

Page 27: ...close with any call to ZONE 1 Zone 1 can be enabled as a priority zone typically used for heating domestic hot water The ZONE 1 E S can be used to close a DHW contact on boiler controls equipped with...

Page 28: ...ZONE6 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORI...

Page 29: ...Freeze Prevention Feature After one hour of a priority demand the control will open the ZONE 1 E S contacts and drop power to PRIORITY PUMP 1 If a call for heat exists from zones 2 6 the control will...

Page 30: ...ONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM AUX 3 Zone ZSR103 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120 VAC L N O...

Page 31: ...ted to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will close with any call to ZONE 1 Zone 1 can be enabled as a priority zone...

Page 32: ...C R W T T COM T STAT 4 C R W T T COM AUX 4 Zone ZSR104 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120 VAC L N O N O F F STATUS DURING...

Page 33: ...act rated up to 120 VAC 2 Amps which is typically connected to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will close with any...

Page 34: ...closed Dry contacts XX AUX ZONE 1 E S capable of switching line voltage Large terminal connections High capacity 40 VA transformer standard for 3 and 4 zone models expandable to 80 VA and 80 VA for th...

Page 35: ...d Power ON LED Dual labeled T stat terminals Compatible with 2 3 and 4 wire T stats Dip switches 120 VAC input power connection Zone valve end switch connection Zone valve motor connections Transforme...

Page 36: ...ttom latch Snap top of transformer into latch arms Feed wiring through hole near the top of the transformer and insert transformer plug into the socket Repeat process for 2nd transformer if using six...

Page 37: ...NSFORMER L PUM T STAT 2 T T COM E S T STAT 3 T T COM T STAT 1 T T COM T STAT 4 T T COM 6 Zone ZSR106 REMOTE ENABLE 24 120 VAC L N L Line hot leg of 120 VAC supply N Neutral of 120 VAC Grounds Input po...

Page 38: ...SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F...

Page 39: ...XX Dry contact rated up to 120 VAC 2 Amps which is typically connected to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will clo...

Page 40: ...MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 END SWITCH MOTOR L SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C...

Page 41: ...close the X X contacts to signal the boiler of a demand When all the thermostat demands are satisfied R to W will open and the T STAT CALL and VALVE OPEN LEDs will turn off The X X contacts will open...

Page 42: ...H MOTOR L SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F...

Page 43: ...e control will close the XX contacts to signal the boiler of a demand When all the thermostat demands are satisfied R toWwillopenandthe T STATCALL and VALVE OPEN LEDs will turn off The XX contacts wil...

Page 44: ...PUMP N STATUS DURING ZONE 1 DEMAND ZONE 1 END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 END SWITCH MOTOR L SYSTEM PUMP N T ST...

Page 45: ...The ZONE 1 E S and X X contacts open If a call for heat exists from zones 2 12 the corresponding T STAT CALL will illuminate again and 24 VAC will be delivered to their zone MOTOR terminals When the z...

Page 46: ...S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4 ZONE 5 ZONE 3 MASTER P...

Page 47: ...mp terminals SYSTEM PUMP Runs when any zone calls for heat SEC PUMP Runs when any zone calls for heat ZONE 1 PUMP Runs when zone 1 thermostat calls for heat and zone 1 end switch has closed A jumper i...

Page 48: ...2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZO...

Page 49: ...boiler of a demand When all the thermostat demands are satisfied R to W will open and the T STAT CALL and VALVE OPEN LEDs will turn off The XX contacts will open terminating the demand for heat to the...

Page 50: ...PUMP EXERCISE ON PRIORITY ON AUX ON SLAVE OFF OFF OFF DURING PRIORITY DEMAND 6 Zone ZVR106 L POWER IN N POWER T SAT CALL ZONE 6 L ZONE 1 PUMP N L SEC PUMP N STATUS DURING ZONE 1 DEMAND ZONE 1 END SWIT...

Page 51: ...will open terminating the demand for heat to the boiler The 120 VAC is dropped to the SYSTEM PUMP and SEC PUMP Description of terminals Ground N Neutral Common leg of 120 VAC L Line Hot leg of 120 VA...

Page 52: ...P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4 ZONE 3 MASTER PUMP EXERCISE ON PRIORITY ON AUX ON SLAVE OF...

Page 53: ...put The control will close the XX contacts to signal the boiler of a demand and close the AUX contacts to signal the ECM pump to start When all the thermostat demands are satisfied R to W will open an...

Page 54: ...COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4...

Page 55: ...ose with any call to ZONE 1 Zone 1 can be enabled as a priority zone typically used for heating domestic hot water The ZONE 1 E S can be used to close a DHW contact on boiler controls equipped with th...

Page 56: ...48 Caleffi North America Inc 3883 W Milwaukee Rd Milwaukee WI 53208 Tel 414 238 2360 Fax 44 238 2366 www caleffi com Ask Us caleffi com Copyright 2016 Caleffi North America Inc...

Reviews: