background image

When a zone has a demand 
from a thermostat (T T / R W ) 

 

the control will send 120 VAC to 
the corresponding zone pump, 
primary pump and the (X X) dry 
contact will close to signal the 
boiler of a heating demand. AUX 

dry contact will also close as a signal to a variable speed self regulated pump or other controls.  
ZONE 1 can be used for priority. When the priority dip switch is ON, a  demand from T-STAT 1 will 
activate PRIORITY PUMP 1 and all other zone pumps will be switched OFF. The Priority has a 1 
hour time out and will go back to operating zones 2 - 6. The ZONE 1 (DHW) dry contact will also 
close. Depending upon "Status During Priority" jumper, the primary pump will either be ON or OFF.

XX

 = Dry contact rated up to 120 VAC, 2 Amps, which is typically 

connected to T T  on boiler control, closes when any zone calls including 
priority. 

ZONE 1 / ES 

(DHW) = Dry contact, rated up to 120 VAC, 2 

Amps, close with any call to ZONE 1, it is typically used to close DHW
contact on boiler controls equipped with these features. 

AUX 

= Dry 

contact, rated up to 120 VAC, 2 Amps, close when any zone calls and 

can be used 

as  signal  to  a variable speed self regulated pump or other controls.

The ZSR series of control is programmed by positioning 
five dip switches for the following operations.

Master / Slave: 

allows for unlimited expansion to 

additional ZSR or ZVR relays boards.

Priority ON / OFF:

 When priority switch is ON, upon 

demand to TSTAT 1 , ZONE 1 will  operate as priority 
and all other zones are temporarily switched off (with 
1 hour time-out). When priority is  OFF, any zones 
that were active when ZONE 1 was switched on will 
remain on.

Remote Enable ON / OFF: 

When remote enable mode is ON, the ZSR board will hold off all zones 

until it receives an external 24 - 120 VAC signal to the Remote Enable terminals. 

Exercise ON / OFF:

 When exercise mode is ON, each circulator is switched on for 30 seconds 

following 72 hours of inactivity.

Post Purge Zone #1 ON / OFF:

 When post purge is ON, Zone 1 pump continues operating for 2 

minutes after the priority zone is switched off.

MASTER

PRIORITY ON

REMOTE ENABLE ON

EXERCISE ON

POST PURGE ZONE#1 ON

SLAVE
OFF
OFF
OFF
OFF

Dip switch settings

ZONE 1

E / S

X X

AUX

Boiler Connections

T-STAT 2

C

R

W

T

T COM

T-STAT 3

C

R

W

T

T COM

T-STAT 1

C

R

W

T

T COM

T-STAT 4

C

R

W

T

T COM

Thermostats

Status During Priority ON / OFF:

 When status jumper 

is placed on the ON pins, the primary pump will 
continue to operate during ZONE 1 priority demand. 
When jumper is placed on the OFF pins, the primary 
pump will be OFF during ZONE 1 priority demand.

PRIMARY

PUMP

L

N

0
/

0

'
'

STATUS 

DURING

PRIORITY

Jumper

Summary of Contents for Z-one ZSR103

Page 1: ...DHW capable of switching line voltage t High capacity transformer t Large terminal connections t Simpli ed wiring with extra ground terminals t Heavy duty sealed relays t All pumps fuse protected with...

Page 2: ...ctrical codes WARNING Avoid electrical noise interference Do not install near large conductors electrical machinery or welding equipment Avoid locations where excessive moisture corrosive fumes vibrat...

Page 3: ...is damaged replace control with functional one Mounting Mount the Caleffi Z one switching relay box to a suitable surface Slotted holes are provided for mounting purposes Do not mount to a surface th...

Page 4: ...edbypositioning five dip switches for the following operations Master Slave allows for unlimited expansion to additional ZSR or ZVR relays boards Priority ON OFF When priority switch is ON upon demand...

Page 5: ...es wiring easy Three extra ground screw terminals connection allows fast grounding of pumps eliminating the need for extra wire connectors Pump terminals have 120 VAC outputs for simpli ed pump connec...

Page 6: ...ZONE2 ZONE3 ZONE4 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM AUX 4 Zone ZSR104 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON...

Page 7: ...MP 3 N TRANSFORMER L N L PUMP 4 N L PUMP 5 N L PUMP 6 N POWER ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4...

Page 8: ...T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120...

Page 9: ...1 1...

Page 10: ...ump can be operated Zone priority is selectable with 1 hour time out feature Other features include pump exercising selectable post purge and 3 pump ground terminals for simpli ed wiring The ZVR Serie...

Page 11: ...zone valve control Product overview 26 Circuit board 27 Cover removal Transformer Installation 28 Product details 29 C1 Mod Con boiler hydro separator zone valves 30 C2 Mod Con boiler indirect DHW on...

Page 12: ...MP 4 N L PUMP 5 N L PUMP 6 N THM 5 C R W T T COM THM 6 C R W T T COM PWR ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 DipSwitches Master Slave Priority OFF Priority ON Primary OFF Primary ON Exercise OFF Exerc...

Page 13: ...g a Taco 570 valve to Caleffi Z one Relay When connecting the Taco 570 zone valve to the Caleffi Z one Relay the wiring of this valve can only be done in one way The left motor terminal on the ZVR ser...

Page 14: ...0 VAC pump with boiler enable or two devices without boiler enable 5 A capacity each relay 10 A total Rear knock outs for mounting onto 4 x4 junction box High capacity 6VA transformer Simplified wirin...

Page 15: ...p connection Dual labeled T stat terminals Compatible with 2 3 and 4 wire T stats Replaceable fuses 6 VA Transformer Keyhole mounting which fits a 4X4 junction box Pre installed jumper Rear knockout f...

Page 16: ...om power zone transformer N L L RELAY 1 C N O N C C N O N C RELAY 2 Calef single zone relay L N A1 Single thermostat Hydronic diagram is for illustration purposes only some components have been remove...

Page 17: ...the thermostat demand is satisfied R to W will open and the ZONE LED will turn off The control will remove power from relays 1 and 2 opening C to NO This will drop 120 VAC to your pump and terminate t...

Page 18: ...N C C N O N C RELAY 2 Calef single zone relay 4 wire zone valve 4 wire zone valve 4 wire zone valve R W 24 VAC T T R W R W End switch wires L N A2 Multiple thermostats Hydronic diagram is for illustr...

Page 19: ...factory installed jumper between L and C When all the thermostat demands are satisfied the zone valves will close and the end switch will open R to W The ZONE LED will turn off The control will remove...

Page 20: ...TRV TRV TRV R W C T T com power zone transformer N L L RELAY 1 C N ON C C N ON C RELAY 2 ZSR101 T T L N A3 Single master thermostat panel radiators with TRVs variable speed pump Hydronic diagram is fo...

Page 21: ...red room temperatures The room temperatures will then be controlled by each individual thermostatic radiator valve by adjusting the flow through the radiator making this a fitting application for a va...

Page 22: ...re Selectable post purge and exercise Dry contacts X X AUX ZONE 1 E S capable of switching line voltage High capacity transformer Large terminal connections Simplified wiring with extra ground termina...

Page 23: ...labeled T stat terminals Compatible with 2 3 and 4 wire T stats Selectable DIP switches LED for each zone 120 VAC zone pump outputs 120 VAC input power connection ZONE1 ES closes only during a demand...

Page 24: ...release from base Roll cover off base Mounting Do not mount to a surface that exceeds 115 F 45 C The unit must be only located in dry interior locations Use only copper conductor supply wire suitable...

Page 25: ...l PRIORITY PUMP Runs when zone 1 calls Can be programmed to be the priority zone L Line hot leg of 120 VAC to power the pump N Neutral leg of 120 VAC to power the pump Remote Enable allows for input o...

Page 26: ...MMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE...

Page 27: ...close with any call to ZONE 1 Zone 1 can be enabled as a priority zone typically used for heating domestic hot water The ZONE 1 E S can be used to close a DHW contact on boiler controls equipped with...

Page 28: ...ZONE6 T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX 6 Zone ZSR106 MASTER PRIORI...

Page 29: ...Freeze Prevention Feature After one hour of a priority demand the control will open the ZONE 1 E S contacts and drop power to PRIORITY PUMP 1 If a call for heat exists from zones 2 6 the control will...

Page 30: ...ONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM AUX 3 Zone ZSR103 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120 VAC L N O...

Page 31: ...ted to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will close with any call to ZONE 1 Zone 1 can be enabled as a priority zone...

Page 32: ...C R W T T COM T STAT 4 C R W T T COM AUX 4 Zone ZSR104 MASTER PRIORITY ON REMOTE ENABLE ON EXERCISE ON POST PURGE ZONE 1 ON SLAVE OFF OFF OFF OFF REMOTE ENABLE 24 120 VAC L N O N O F F STATUS DURING...

Page 33: ...act rated up to 120 VAC 2 Amps which is typically connected to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will close with any...

Page 34: ...closed Dry contacts XX AUX ZONE 1 E S capable of switching line voltage Large terminal connections High capacity 40 VA transformer standard for 3 and 4 zone models expandable to 80 VA and 80 VA for th...

Page 35: ...d Power ON LED Dual labeled T stat terminals Compatible with 2 3 and 4 wire T stats Dip switches 120 VAC input power connection Zone valve end switch connection Zone valve motor connections Transforme...

Page 36: ...ttom latch Snap top of transformer into latch arms Feed wiring through hole near the top of the transformer and insert transformer plug into the socket Repeat process for 2nd transformer if using six...

Page 37: ...NSFORMER L PUM T STAT 2 T T COM E S T STAT 3 T T COM T STAT 1 T T COM T STAT 4 T T COM 6 Zone ZSR106 REMOTE ENABLE 24 120 VAC L N L Line hot leg of 120 VAC supply N Neutral of 120 VAC Grounds Input po...

Page 38: ...SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F...

Page 39: ...XX Dry contact rated up to 120 VAC 2 Amps which is typically connected to TT on boiler control closes when any zone calls including priority ZONE 1 E S Dry contact rated up to 120 VAC 2 Amps will clo...

Page 40: ...MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 END SWITCH MOTOR L SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C...

Page 41: ...close the X X contacts to signal the boiler of a demand When all the thermostat demands are satisfied R to W will open and the T STAT CALL and VALVE OPEN LEDs will turn off The X X contacts will open...

Page 42: ...H MOTOR L SYSTEM PUMP N T STAT 2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F...

Page 43: ...e control will close the XX contacts to signal the boiler of a demand When all the thermostat demands are satisfied R toWwillopenandthe T STATCALL and VALVE OPEN LEDs will turn off The XX contacts wil...

Page 44: ...PUMP N STATUS DURING ZONE 1 DEMAND ZONE 1 END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 END SWITCH MOTOR L SYSTEM PUMP N T ST...

Page 45: ...The ZONE 1 E S and X X contacts open If a call for heat exists from zones 2 12 the corresponding T STAT CALL will illuminate again and 24 VAC will be delivered to their zone MOTOR terminals When the z...

Page 46: ...S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4 ZONE 5 ZONE 3 MASTER P...

Page 47: ...mp terminals SYSTEM PUMP Runs when any zone calls for heat SEC PUMP Runs when any zone calls for heat ZONE 1 PUMP Runs when zone 1 thermostat calls for heat and zone 1 end switch has closed A jumper i...

Page 48: ...2 C R W T T COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZO...

Page 49: ...boiler of a demand When all the thermostat demands are satisfied R to W will open and the T STAT CALL and VALVE OPEN LEDs will turn off The XX contacts will open terminating the demand for heat to the...

Page 50: ...PUMP EXERCISE ON PRIORITY ON AUX ON SLAVE OFF OFF OFF DURING PRIORITY DEMAND 6 Zone ZVR106 L POWER IN N POWER T SAT CALL ZONE 6 L ZONE 1 PUMP N L SEC PUMP N STATUS DURING ZONE 1 DEMAND ZONE 1 END SWIT...

Page 51: ...will open terminating the demand for heat to the boiler The 120 VAC is dropped to the SYSTEM PUMP and SEC PUMP Description of terminals Ground N Neutral Common leg of 120 VAC L Line Hot leg of 120 VA...

Page 52: ...P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4 ZONE 3 MASTER PUMP EXERCISE ON PRIORITY ON AUX ON SLAVE OF...

Page 53: ...put The control will close the XX contacts to signal the boiler of a demand and close the AUX contacts to signal the ECM pump to start When all the thermostat demands are satisfied R to W will open an...

Page 54: ...COM COMMS D P ZONE 1 E S X X T STAT 3 C R W T T COM T STAT 1 C R W T T COM T STAT 4 C R W T T COM T STAT 5 C R W T T COM T STAT 6 C R W T T COM AUX O N O F F O N O F F VALVE OPEN ZONE 1 ZONE 2 ZONE 4...

Page 55: ...ose with any call to ZONE 1 Zone 1 can be enabled as a priority zone typically used for heating domestic hot water The ZONE 1 E S can be used to close a DHW contact on boiler controls equipped with th...

Page 56: ...48 Caleffi North America Inc 3883 W Milwaukee Rd Milwaukee WI 53208 Tel 414 238 2360 Fax 44 238 2366 www caleffi com Ask Us caleffi com Copyright 2016 Caleffi North America Inc...

Reviews: