Disinfection interruption:

Disinfection can be interrupted while it is still in progress, with the following modes:
- holding down the knob for 10 seconds and confirming the "Disinfection stop” control
- from the "Programming Menu", setting the disinfection control to OFF
- opening the inlet IN2 contact (normally closed)
- remotely through the optional board CS179.
At the end of disinfection, the device performs a zero acquisition and returns in water mixing mode indicating the failed disinfection, if any.

Disinfection activation with connection through inlet IN1

MODE

START

END

DESCRIPTION

Manual activation 

through switch

Manual end 

through switch

Disinfection status persists even beyond the 

maximum time set tHi diS and ends with the 

manual opening of the contact

               (default) 

Manual activation 

through switch

Automatic end

or through switch

The disinfection status persists up to the maximum 

time set tHi diS or with the manual opening of the 

contact

Manual activation 

through button

Automatic end

The disinfection status ends as soon as the 

minimum disinfection time tmin diS is exceeded or 

within the maximum set time tHi diS

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

4 - Thermal shock in progress:

 Thermal shock in progress with control on flow probe T1. During the thermal shock, the following two screens are shown alternating on the display. The 
alternating parts are in orange.

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

6   

Σ

t

s

tmin dis

t1 = 10’

t2 = 5’

t3 = 15’

diS °C

Flow temperature

60°C

Flow temperature

Example with ECO function enabled.

Disinfection code: d1 - ECO function

Flow temperature = Maximum available temperature
Minimum disinfection time = automatic check

Area where time is counted

When the temperature drops below 60°C, the 
countdown stops and resumes from zero when it 
returns above this value.

Disinfection is considered successful when the 
following conditions are continuously respected:
Flow temperature ≥ 60°C 

 minimum time = 36’ 

Flow temperature ≥ 65°C 

 minimum time = 18’

Flow temperature ≥ 70°C 

 minimum time = 12’

IMPORTANT: The activation of the disinfection through the inlet IN1 does not exclude the programmed disinfection.

Summary of Contents for LEGIOMIX 6000 series

Page 1: ...and default values Display menu Programming Menu Installer Menu Alarm management General diaphragm 2 3 6 8 7 10 11 14 PROGRAMMING MANUAL Copyright 2018 Caleffi H0004567 01 www caleffi com Disinfection...

Page 2: ...ved It is recommended to refer to the alarm section in this manual For correct battery installation see the Installation and commissioning manual supplied in the package When the battery checks are co...

Page 3: ...evice does not perform the disinfection Operating status During the operation of the device the following work states can be displayed 1 Reached setpoint 2 Adjustment in progress 3 Disinfection in pro...

Page 4: ...rts are in orange b Disinfection in progress with control on return probe T2 see table on page 5 In this mode the device performs thermal disinfection which consists in raising the mixed water tempera...

Page 5: ...be T1 d2 Disinfection performed at the minimum disinfection temperature diS C Disinfection check performed on probe T1 Disinfection type with recirculation probe T2 enabled Disinfection Code Descripti...

Page 6: ...set tHi diS or with the manual opening of the contact Manual activation through button Automatic end The disinfection status ends as soon as the minimum disinfection time tmin diS is exceeded or withi...

Page 7: ...Reset alarms control Additionally the zero acquisition mode is activated whenever an electric supply failure occurs for at least 60 minutes and at the outlet from any disinfection thermal shock It is...

Page 8: ...om 00 to 99 17 14 Time format selection 12H 24H 24H 15 Hours minutes setting 0 23 hours 0 59 minutes 00 00 16 Daylight saving time setting YES on NO off On 17 Disinfection program change d1 d2 d2 18 T...

Page 9: ...hatever status the appliance is in it is always possible to navigate around the various menus to read and change the various settings The general menu structure is as follows Display menu Press the kn...

Page 10: ...or the day set is displayed the segment below the number indicates its activation Maximum time within which it is possible to perform the disinfection Maximum flow temperature limit it is a system pro...

Page 11: ...uring which the temperature must remain above the set temperature for the thermal shock Setting the maximum time available within which it is possible to perform the thermal shock RESET Control to res...

Page 12: ...x time bands that can be set for recirculation OUT2 activation 1 02 00 and 05 59 4 14 00 and 17 59 2 06 00 and 09 59 5 18 00 and 21 59 3 10 00 and 13 59 6 22 00 and 01 59 Installer Menu password chang...

Page 13: ...of the valve Perform with closed shut off valves The number of times the error has occurred appears in the top right of the screen To delete the alarms from the sub menu use the Reset Alarms Installe...

Page 14: ...F RESETTING BLOCKING ALARM The device resumes its operation when the probe T1 returns to the set value Alarm management To make it easier to resolve any functional faults that occur after installation...

Page 15: ...er mixing status the first successful disinfection clears the alarm condition but records it in the log of the last failed disinfections the display shows the symbol Manual YES it is also recorded in...

Page 16: ...failure for more than 60 minutes NON BLOCKING ALARM When the electric supply is restored it resumes normal operation after performing the zero acquisition AL08 FAULTY FLOW PROBE SELF RESETTING BLOCKIN...

Page 17: ...NC Closed OUT2 Closed OUT3 Open The device can only perform the water mixing while maintaining the alarm active YES PROBE T2 NOT CONNECTED OR DAMAGED Check that the probe is present and correctly con...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Reviews: