background image

12

Set summer daylight saving time. 
ON/OFF selection: activating 
the ON option will enable the 
function. Check the disinfection 
programming.

Disinfection program setting.

Disinfection mode selection 
activated by inlet IN1.

ECO function enable. ON/OFF 
selection: Activate the ON option to 
enable the function.

Setting the minimum disinfection 
temperature, performed on the 
enabled probe (see probes T1 and 
T2 enable control).

Setting disinfection start day and 
time (The segment under the day 
indicates its activation).

Setting the minimum time during 
which the temperature must remain 
above the set temperature during 
the disinfection phase.

Setting of maximum time available 
in which it is possible to perform 
the disinfection.

Setting of the six time bands 
that can be set for recirculation 
   (OUT2 activation)
1-02:00 and 05:59    4-14:00 and 17:59
2-06:00 and 09:59    5-18:00 and 21:59
3-10:00 and 13:59    6-22:00 and 01.59

“Installer Menu” password change.

Access to the "Controls sub-
menu": Zero acquisition, full scale 
acquisition, disinfection, thermal 
shock, test (opening/closing). For 
details of the sub-menu, refer to the 
next paragraph.

Indicates the motor position.

Alarm reset. Resets active and 
historicized alarms. The "Alarm 
Sub-menu" will no longer be 
displayed until the next alarm. For 
details on the sub-menu, refer to 
the relevant paragraph.

Measurement of the associated 
valve.

Exit from "Installer Menu"
After a 2 minute time without 
touching the knob, the menu 
closes automatically 
Programming.

Communication protocol parity 
setting.

Default ON

Default d2

Default In2

Default OFF

Default 60°C

Default 30 min.

Default 60 min.

Active default on all ranges

Default: Every day 02:00

Default: EVEN

Summary of Contents for LEGIOMIX 6000 series

Page 1: ...and default values Display menu Programming Menu Installer Menu Alarm management General diaphragm 2 3 6 8 7 10 11 14 PROGRAMMING MANUAL Copyright 2018 Caleffi H0004567 01 www caleffi com Disinfection...

Page 2: ...ved It is recommended to refer to the alarm section in this manual For correct battery installation see the Installation and commissioning manual supplied in the package When the battery checks are co...

Page 3: ...evice does not perform the disinfection Operating status During the operation of the device the following work states can be displayed 1 Reached setpoint 2 Adjustment in progress 3 Disinfection in pro...

Page 4: ...rts are in orange b Disinfection in progress with control on return probe T2 see table on page 5 In this mode the device performs thermal disinfection which consists in raising the mixed water tempera...

Page 5: ...be T1 d2 Disinfection performed at the minimum disinfection temperature diS C Disinfection check performed on probe T1 Disinfection type with recirculation probe T2 enabled Disinfection Code Descripti...

Page 6: ...set tHi diS or with the manual opening of the contact Manual activation through button Automatic end The disinfection status ends as soon as the minimum disinfection time tmin diS is exceeded or withi...

Page 7: ...Reset alarms control Additionally the zero acquisition mode is activated whenever an electric supply failure occurs for at least 60 minutes and at the outlet from any disinfection thermal shock It is...

Page 8: ...om 00 to 99 17 14 Time format selection 12H 24H 24H 15 Hours minutes setting 0 23 hours 0 59 minutes 00 00 16 Daylight saving time setting YES on NO off On 17 Disinfection program change d1 d2 d2 18 T...

Page 9: ...hatever status the appliance is in it is always possible to navigate around the various menus to read and change the various settings The general menu structure is as follows Display menu Press the kn...

Page 10: ...or the day set is displayed the segment below the number indicates its activation Maximum time within which it is possible to perform the disinfection Maximum flow temperature limit it is a system pro...

Page 11: ...uring which the temperature must remain above the set temperature for the thermal shock Setting the maximum time available within which it is possible to perform the thermal shock RESET Control to res...

Page 12: ...x time bands that can be set for recirculation OUT2 activation 1 02 00 and 05 59 4 14 00 and 17 59 2 06 00 and 09 59 5 18 00 and 21 59 3 10 00 and 13 59 6 22 00 and 01 59 Installer Menu password chang...

Page 13: ...of the valve Perform with closed shut off valves The number of times the error has occurred appears in the top right of the screen To delete the alarms from the sub menu use the Reset Alarms Installe...

Page 14: ...F RESETTING BLOCKING ALARM The device resumes its operation when the probe T1 returns to the set value Alarm management To make it easier to resolve any functional faults that occur after installation...

Page 15: ...er mixing status the first successful disinfection clears the alarm condition but records it in the log of the last failed disinfections the display shows the symbol Manual YES it is also recorded in...

Page 16: ...failure for more than 60 minutes NON BLOCKING ALARM When the electric supply is restored it resumes normal operation after performing the zero acquisition AL08 FAULTY FLOW PROBE SELF RESETTING BLOCKIN...

Page 17: ...NC Closed OUT2 Closed OUT3 Open The device can only perform the water mixing while maintaining the alarm active YES PROBE T2 NOT CONNECTED OR DAMAGED Check that the probe is present and correctly con...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Reviews: