background image

UG-7-A6O Installation manual 

 

page 2

 

HFE716 Version: 14 

 

Date: 2014-03-24

 

[1] LIMITATIONS OF DUCT SMOKE DETECTORS 

 

 

The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS 
A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are 
they a substitute for early warning in a building’s regular fire detection system. Calectro AB supports this 
position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. UG-7-A6O is listed per 
UL 268A. This device will not operate without electrical power supplied to it. Fire situations may cause an 
interruption of power. The system safeguards should be discussed with your local fire protection specialist. This 
device will not sense smoke unless the ventilation system is operating and the cover is installed. For this detector 
to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector 
MUST be operated within ALL electrical and environmental specifications listed in this manual. Failure to 
comply with these requirements may prevent the detector from activating when smoke is present in the air duct. 

 
[2] OVERVIEW OF UG-7-A6O COMPONENTS 

 

Figure 1. 

 

 

 

 
 

ITEM NO.   DESCRIPTION  

Test hole plug 

4 x Delta PT 60x30 

Cover gasket 

Cover / label area 

Smoke detector  

10 x Delta PT 40x8 

Smoke detector base 

Electronics PCB 

Inner cover 

10 

Base part 

11 

Seal gasket 

12 

O-ring  

13 

Sampling tube  

14 

Outer cover 

15 

End plug 

16 

Test/Reset button gasket 

A1 * 

Diverter 

* Item A1: Diverter UG-7-DV-T2 
for air velocities below 300ft/m. 
Assembly: Remove the cover (item 
4, Figure 1), place the diverter on 
the air inlet part so it covers half the 
smoke detector (item 5). 
Note: Do not use the diverter for 
application that exceeds 300 f/m. 
 
 
 

1

 

3

 

2

 

4

 

6

 

8

 

7

 

9

 

10

 

14

 

11

 

16

 

13

 

5

 

12

 

15

 

A1

 

Summary of Contents for UG-7-A6O-120V

Page 1: ... at 120Vac Max alarm current 83mA 145mA 42mA at 120Vac Link current 5mA Total max auxiliary current output on terminals 2 and 5 Without linked detectors 30mA with linked detectors 25mA Contact ratings Alarm initiation contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Supervisory contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Alarm auxiliary contacts DPDT 10A 30VDC resistive 10A 25...

Page 2: ...cover is installed For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 OVERVIEW OF UG 7 A6O COMPONENTS Fi...

Page 3: ...4 DUCT SMOKE DETECTOR KIT CONTENTS 1 Detector power board assembly and covers 2 Three metal screws for mounting 3 One sampling tube end plug 4 Installation manual this document NOTE Cable glands are not included in the kit NOTE A sampling tube must be ordered to complete the installation The sampling tube should penetrate approx 90 of the width of the duct See Table 4 1 to determine the sampling t...

Page 4: ...mounted Measure the diameter of the duct The sampling tube should penetrate approximately 90 of the width of the duct See Section 4 Table 4 1 If necessary shorten the sampling tube and insert the end plug Figure 5 NOTE When installing sampling tubes longer than 2 ft see Section 5 4 Insert the sampling tube in the Base Part Figure 6 Secure the sampling tube by fastening the screw Figure 7 Insert th...

Page 5: ...the round plastic wall in the selected entry and insert a conduit connector If the factory prepared opening is not used it must be properly sealed Figure 14a Remove the four screws and lift of the cover according to Figure 14b in order to be able to make the wiring Place the cover back on the housing and tighten the four screws for proper mounting please use torque 1 8 1 9 Nm 6 2 DETECTOR LINKING ...

Page 6: ...d detectors 25mA max load 6 External Reset Test input Short circuit to terminal 1 GND Test Reset alarm 7 Supervisory relay NC Indicates contaminated detector removed detector or power failure 8 Supervisory relay Common Indicates contaminated detector removed detector or power failure 9 Alarm relay NO Smoke alarm relay 10 Alarm relay Common Smoke alarm relay 11 Auxiliary relay 1 NO Auxiliary relay ...

Page 7: ...al power supply information NOTE 3 Auxiliary contacts shown in standby position Contacts switch during alarm as indicated by arrows Auxiliary contacts are not to be used for connection to the control panel See specifications for contact ratings Fire control panel Alarm initiation loop End of line resistor specified by panel manufacturer Alarm initiation contact in standby position 9 N O 10 C 7 8 C...

Page 8: ...o indicates that the aerosol smoke is ventilated from the detector chamber Once this operation is completed the inch 6 35mm hole must be sealed off by applying duct tape NOTE Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard com model HO 25S Smoke Detector Tester Proper use of the canned smoke agent will place the smoke detector in alarm mode Refer to the manufacture s...

Page 9: ... INDICATION Detector condition is indicated by the detector LED and the corresponding LEDs on the power board The power board has four separate LEDs to indicate the status of the detector Refer to Table 8 1 for more details Table 8 1 Status Description Detector LED red Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminals open Terminals closed Standby Detector in normal...

Page 10: ...t Table 9 1 for more information External Reset Test input shorted Terminals 1 and 6 This will deactivate all relays except the Smoke Alarm Relay Consult Table 9 1 for more information Verify the execution of all intended auxiliary functions i e fan shutdown damper control etc Table 9 1 Action Description Detector LED Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminal...

Page 11: ...ector base This can be ordered from Calectro AB Please see contact information in this Installation manual 7 Install two 9V batteries in the UB 6 base according to Figure 20 8 Mount the detector head in the UB 6 base 9 Perform the Fast ramp sensitivity test with the Trutest device according to the Trutester User Manual 10 The sensitivity range is 3 36 to 4 42 ft 11 Replace the detector head in the...

Page 12: ...horities testing has been completed and the smoke detector system is back in operation Remove the diverter if installed 2 Replace the diverter if installed See Figure 1 1 10 3 DETECTOR REPLACEMENT If the detector needs to be replaced do the following 1 Disconnect the power 2 Remove the four screws and the cover as described in Section 6 1 Figure 14b 3 Remove the detector head by turning it counter...