background image

UG-7-A6O Installation manual 

 

page 8

 

HFE716 Version: 14 

 

Date: 2014-03-24

 

NOTE 4:

 Supervisory contacts indicates: removed, contaminated or power failure. Contacts shown in standby 

position. Open contacts indicate a trouble condition. See specifications for contact ratings.  
 

NOTE 5:

 Alarm Initiation contacts shown in standby position. Closed contacts indicate an alarm condition. See 

specifications for contact rating. 
 

NOTE 6:

 The detector link circuit must be a loop. This means that the last linked detector must be connected 

with the first detector. Maximum 100 detectors in a link. Maximum cable length: 200 yards between each 
detector. Disconnect the power when installing the detector linking function. Polarity must be maintained 
between all linked detectors to obtain normal operation of the linking function. 
 
 

[7] MEASUREMENT TESTS 
 
[7.1] METHOD 1: AEROSOL SPRAY FOR AIR FLOW SPEED: 100-275 FPM 

 
This test is aimed toward a system that operates between 100-275 FPM. Additional modifications will be 
required for a system that operates at higher air velocities that exceeds 275 FPM. This will require drilling an 
approximately ¼ inch (6.35mm) hole about 3 feet (0.914m) upstream from the duct detector. Measure the air 
movement through the hole with a velocity meter while the air handler is on, the air velocity should be a 
minimum of 100 FPM Introduce aerosol smoke into the duct through the ¼ inch (6.35mm) hole by following the 
instruction on the smoke detector tester and wait approximately 2-3 minutes for the detector to alarm. The 
detector alarm indicates that air is moving into the detector. 
With the air handler on, push the Reset Button (repeatedly if necessary) until the UG-7-A6O remains in Standby 
condition. This also indicates that the aerosol smoke is ventilated from the detector chamber. Once this operation 
is completed, the ¼ inch (6.35mm) hole must be sealed off by applying duct tape. 

 
NOTE:

 Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard.com, model HO-

25S Smoke Detector Tester. Proper use of the canned smoke agent will place the smoke detector in alarm mode. 
Refer to the manufacture’s details and instructions for the proper use of the canned smoke agent. 

 
[7.2] METHOD 2: LOW VELOCITY 100-500 FPM: 
This test is intended for low-flow systems (100-500 FPM).

 

 
With the air handler on, measure the air velocity with an anemometer. The air speed must be100 FPM or 
greater. Then use the Dwyer Transmitter (series 607) by following the details provided in figure 16B. The 
pressure differential across the inlet port and outlet ports of the sampling tube shall be verified to be more than 
0.01 inches of water. Measure the pressure difference between the inlet port and outlet ports on the sampling 
tube with a Dwyer Series 607 Differential Pressure Transmitter. To verify sufficient sampling of ducted air, turn 
the air handler on. Connect the leads of the meter to either side of the 1KΩ resistor. Allow unit to warm up for 
15 seconds. With both HIGH and LOW pressure ports open to ambient air, measure and record the voltage drop 
across the 1KΩ resistor (measurement A), typical reading is approximately 4V. Use flexible tubing to connect 
the HIGH side of the transmitter to the inlet port of the sampling tube and the LOW side of the transmitter to the 
outlet ports of the sampling tube. Measure and record the voltage drop across the 1KΩ resistor (measurement 
B). Subtract the voltage recorded in measurement A from the voltage recorded in measurement B.  The results 
should be greater than 0.15 volts, and then this indicates that there is enough air flow through the duct smoke 
detector for proper operation. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for UG-7-A6O-120V

Page 1: ... at 120Vac Max alarm current 83mA 145mA 42mA at 120Vac Link current 5mA Total max auxiliary current output on terminals 2 and 5 Without linked detectors 30mA with linked detectors 25mA Contact ratings Alarm initiation contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Supervisory contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Alarm auxiliary contacts DPDT 10A 30VDC resistive 10A 25...

Page 2: ...cover is installed For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 OVERVIEW OF UG 7 A6O COMPONENTS Fi...

Page 3: ...4 DUCT SMOKE DETECTOR KIT CONTENTS 1 Detector power board assembly and covers 2 Three metal screws for mounting 3 One sampling tube end plug 4 Installation manual this document NOTE Cable glands are not included in the kit NOTE A sampling tube must be ordered to complete the installation The sampling tube should penetrate approx 90 of the width of the duct See Table 4 1 to determine the sampling t...

Page 4: ...mounted Measure the diameter of the duct The sampling tube should penetrate approximately 90 of the width of the duct See Section 4 Table 4 1 If necessary shorten the sampling tube and insert the end plug Figure 5 NOTE When installing sampling tubes longer than 2 ft see Section 5 4 Insert the sampling tube in the Base Part Figure 6 Secure the sampling tube by fastening the screw Figure 7 Insert th...

Page 5: ...the round plastic wall in the selected entry and insert a conduit connector If the factory prepared opening is not used it must be properly sealed Figure 14a Remove the four screws and lift of the cover according to Figure 14b in order to be able to make the wiring Place the cover back on the housing and tighten the four screws for proper mounting please use torque 1 8 1 9 Nm 6 2 DETECTOR LINKING ...

Page 6: ...d detectors 25mA max load 6 External Reset Test input Short circuit to terminal 1 GND Test Reset alarm 7 Supervisory relay NC Indicates contaminated detector removed detector or power failure 8 Supervisory relay Common Indicates contaminated detector removed detector or power failure 9 Alarm relay NO Smoke alarm relay 10 Alarm relay Common Smoke alarm relay 11 Auxiliary relay 1 NO Auxiliary relay ...

Page 7: ...al power supply information NOTE 3 Auxiliary contacts shown in standby position Contacts switch during alarm as indicated by arrows Auxiliary contacts are not to be used for connection to the control panel See specifications for contact ratings Fire control panel Alarm initiation loop End of line resistor specified by panel manufacturer Alarm initiation contact in standby position 9 N O 10 C 7 8 C...

Page 8: ...o indicates that the aerosol smoke is ventilated from the detector chamber Once this operation is completed the inch 6 35mm hole must be sealed off by applying duct tape NOTE Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard com model HO 25S Smoke Detector Tester Proper use of the canned smoke agent will place the smoke detector in alarm mode Refer to the manufacture s...

Page 9: ... INDICATION Detector condition is indicated by the detector LED and the corresponding LEDs on the power board The power board has four separate LEDs to indicate the status of the detector Refer to Table 8 1 for more details Table 8 1 Status Description Detector LED red Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminals open Terminals closed Standby Detector in normal...

Page 10: ...t Table 9 1 for more information External Reset Test input shorted Terminals 1 and 6 This will deactivate all relays except the Smoke Alarm Relay Consult Table 9 1 for more information Verify the execution of all intended auxiliary functions i e fan shutdown damper control etc Table 9 1 Action Description Detector LED Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminal...

Page 11: ...ector base This can be ordered from Calectro AB Please see contact information in this Installation manual 7 Install two 9V batteries in the UB 6 base according to Figure 20 8 Mount the detector head in the UB 6 base 9 Perform the Fast ramp sensitivity test with the Trutest device according to the Trutester User Manual 10 The sensitivity range is 3 36 to 4 42 ft 11 Replace the detector head in the...

Page 12: ...horities testing has been completed and the smoke detector system is back in operation Remove the diverter if installed 2 Replace the diverter if installed See Figure 1 1 10 3 DETECTOR REPLACEMENT If the detector needs to be replaced do the following 1 Disconnect the power 2 Remove the four screws and the cover as described in Section 6 1 Figure 14b 3 Remove the detector head by turning it counter...

Reviews: