UG-7-A6O Installation manual
page 10
HFE716 Version: 14
Date: 2014-03-24
[9] CONFIRMATION OF OPERATION
[9.1] POWERING THE UNIT
Apply power to terminals 17 and 18:
24 VAC/DC for UG-7-A6O-24V version.
120 VAC for UG-7-A6O-120V version.
[9.2] PERFORM DETECTOR CHECK
Verify that the UG-7-A6O is installed according to this manual and that it is in Standby Status according to
Table 8.1.
[9.3] SENSITIVITY VERIFICATION
The UG-7-A6O indicates that the smoke detector is contaminated
and should be replaced. The indications are:
Flashing the amber LED number 3 and opening of the relay contact terminals 7 and 8.
[9.4] DETECTOR CLEANING PROCEDURES
Notify the local and responsible authorities that maintenance is being conducted on the smoke detector system,
and that the system will be out of service until maintenance is completed. Disable the zone or system that is
under maintenance to avoid unwanted alarms and/or the possibility fire department unnecessary dispatch.
[9.4.1] RELAY TEST – EXCEPT SMOKE ALARM RELAY
Reset/Test Button - Press and hold the test button located on the side of the power board cover. This will
deactivate all relays except the Smoke Alarm Relay. Consult
Table 9.1
for more information.
External Reset/Test input shorted (Terminals 1 and 6). This will deactivate all relays except the Smoke Alarm
Relay. Consult
Table 9.1
for more information.
Verify the execution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.).
Table 9.1
Action
Description
Detector
LED
Power board LED
number
Status of relays
1
Green
2
Yellow
3
Yellow
4
Red
Terminals
open
Terminals
closed
Pressed Reset/Test
Button or short
Terminals 1 and 6
Test of all LED/relays
except Smoke Alarm
LED/relay
7-8
9-10
12-13
15-16
11-12
14-15
[9.4.2] SMOKE RESPONSE AND ALARM RELAY TEST
To test the Smoke Alarm Relay and LEDs, open the test hole by lifting the test hole plug.
Figure 19.
Spray
aerosol smoke* through the test hole. Wait approximately 20 seconds for the detector to alarm. If the air speed in
the duct is high, it may be required to repeat the test due to high dilution of the aerosol smoke.
NOTE:
Verify that the Test Hole Plug is replaced after the test.
Consult
Table 8.1
(Alarm status) for more details.
* Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard.com, model HO-25S
Smoke Detector Tester. Proper use of the canned smoke agent will place the smoke detector in alarm mode.
Refer to the manufacture’s details and instructions for the proper use of the canned smoke agent.
Figure 19
Test hole plug