background image

UG-7-A6O Installation manual 

 

page 5

 

HFE716 Version: 14 

 

Date: 2014-03-24

 

  Figure 6 

                      Figure 7 

 

Figure 8 

      

 

 

 
[5.4] INSTALLATION OF SAMPLING TUBE LONGER THAN 2 FT. 

Strong vibrations can arise inside a duct due to the air currents. When the 

diameter of the duct is larger than 2 ft. 

the sampling tube should penetrate the whole duct. Drill a 2 inch hole in the opposite side of the duct. Mount the 
rubber gasket HFU204* in the hole. Put on the long plastic end plug HFU640* on the sampling tube. The 
sampling tube should not protrude more than 1 inch through the duct wall in order to avoid air leakage. 

Figure 

12.

 

* Delivered together with sampling tubes of 5 and 9 ft. 

 

Figure 12 

 
 

 
 
 
 
 
 
 
 
[6] FIELD WIRING INSTALLATION GUIDELINES 

All wiring must be installed in compliance with the National Electrical Code and the local codes having 
jurisdiction. Appropriate wire gauges should be used. Color-Code the conductors used to connect smoke 
detectors to control panels and accessory devices to avoid wiring problems. Improper connections can prevent a 
system from operating and responding properly in the event of a fire condition. A minimum 18 gauge wire must 
be used for signal wiring (when interconnecting detectors or between detectors and auxiliary devices) 
 

[6.1] CONDUIT ENTRIES AND WIRING 

The UG-7-A6O is factory prepared with one conduit opening. In case more than one opening is needed, carefully 
remove the round plastic wall in the selected entry and insert a conduit connector. If the factory prepared 
opening is not used, it must be properly sealed. 

Figure 14a.  

Remove the four screws and lift of the cover according to 

Figure 14b

 in order to be able to make the wiring. 

Place the cover back on the housing, and tighten the four screws – for proper mounting, please use torque:  1.8-
1.9 Nm. 

 
[6.2] DETECTOR LINKING 

UG-7-A6O has linking function that allows interconnection between maximum 100 units. All linked detectors 
operate independently from each other. The linking function is to be seen as an extra prevention feature that 
could close dampers or stop fans further away in the ventilation system, before the smoke has reached the places 
were the linked detectors are installed. Maximum 200 yards cable length between each detector. The detector 
link circuit must be a loop. This means that the last linked detector must be connected with the first detector. 
Linking function: When one of the linked UG-7-A6O goes into smoke alarm, all other detectors AUX relays are 
activated. The smoke alarm can only be reset on the UG-7-A6O that initiated the smoke alarm. This also resets 
the AUX relays on all linked detectors in the loop. To test the linking function: press and hold the Test/Reset 
button (or short circuit between terminals 6 and 1) for more than 10 seconds on one of the linked detectors.  
For wiring information, see 

Figure 16.

 

 
NOTE:

 Disconnect the power when installing the detector linking function. 

 
Consult 

Figure 16

 and 

Table 8.1

 for more information 

1

 

2

 

3

 

 

HFU204 

HFU640 

>2 ft. 

Summary of Contents for UG-7-A6O-120V

Page 1: ... at 120Vac Max alarm current 83mA 145mA 42mA at 120Vac Link current 5mA Total max auxiliary current output on terminals 2 and 5 Without linked detectors 30mA with linked detectors 25mA Contact ratings Alarm initiation contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Supervisory contacts SPST 1 0A 24VDC resistive 1 0A 120VAC resistive Alarm auxiliary contacts DPDT 10A 30VDC resistive 10A 25...

Page 2: ...cover is installed For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 OVERVIEW OF UG 7 A6O COMPONENTS Fi...

Page 3: ...4 DUCT SMOKE DETECTOR KIT CONTENTS 1 Detector power board assembly and covers 2 Three metal screws for mounting 3 One sampling tube end plug 4 Installation manual this document NOTE Cable glands are not included in the kit NOTE A sampling tube must be ordered to complete the installation The sampling tube should penetrate approx 90 of the width of the duct See Table 4 1 to determine the sampling t...

Page 4: ...mounted Measure the diameter of the duct The sampling tube should penetrate approximately 90 of the width of the duct See Section 4 Table 4 1 If necessary shorten the sampling tube and insert the end plug Figure 5 NOTE When installing sampling tubes longer than 2 ft see Section 5 4 Insert the sampling tube in the Base Part Figure 6 Secure the sampling tube by fastening the screw Figure 7 Insert th...

Page 5: ...the round plastic wall in the selected entry and insert a conduit connector If the factory prepared opening is not used it must be properly sealed Figure 14a Remove the four screws and lift of the cover according to Figure 14b in order to be able to make the wiring Place the cover back on the housing and tighten the four screws for proper mounting please use torque 1 8 1 9 Nm 6 2 DETECTOR LINKING ...

Page 6: ...d detectors 25mA max load 6 External Reset Test input Short circuit to terminal 1 GND Test Reset alarm 7 Supervisory relay NC Indicates contaminated detector removed detector or power failure 8 Supervisory relay Common Indicates contaminated detector removed detector or power failure 9 Alarm relay NO Smoke alarm relay 10 Alarm relay Common Smoke alarm relay 11 Auxiliary relay 1 NO Auxiliary relay ...

Page 7: ...al power supply information NOTE 3 Auxiliary contacts shown in standby position Contacts switch during alarm as indicated by arrows Auxiliary contacts are not to be used for connection to the control panel See specifications for contact ratings Fire control panel Alarm initiation loop End of line resistor specified by panel manufacturer Alarm initiation contact in standby position 9 N O 10 C 7 8 C...

Page 8: ...o indicates that the aerosol smoke is ventilated from the detector chamber Once this operation is completed the inch 6 35mm hole must be sealed off by applying duct tape NOTE Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard com model HO 25S Smoke Detector Tester Proper use of the canned smoke agent will place the smoke detector in alarm mode Refer to the manufacture s...

Page 9: ... INDICATION Detector condition is indicated by the detector LED and the corresponding LEDs on the power board The power board has four separate LEDs to indicate the status of the detector Refer to Table 8 1 for more details Table 8 1 Status Description Detector LED red Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminals open Terminals closed Standby Detector in normal...

Page 10: ...t Table 9 1 for more information External Reset Test input shorted Terminals 1 and 6 This will deactivate all relays except the Smoke Alarm Relay Consult Table 9 1 for more information Verify the execution of all intended auxiliary functions i e fan shutdown damper control etc Table 9 1 Action Description Detector LED Power board LED number Status of relays 1 Green 2 Yellow 3 Yellow 4 Red Terminal...

Page 11: ...ector base This can be ordered from Calectro AB Please see contact information in this Installation manual 7 Install two 9V batteries in the UB 6 base according to Figure 20 8 Mount the detector head in the UB 6 base 9 Perform the Fast ramp sensitivity test with the Trutest device according to the Trutester User Manual 10 The sensitivity range is 3 36 to 4 42 ft 11 Replace the detector head in the...

Page 12: ...horities testing has been completed and the smoke detector system is back in operation Remove the diverter if installed 2 Replace the diverter if installed See Figure 1 1 10 3 DETECTOR REPLACEMENT If the detector needs to be replaced do the following 1 Disconnect the power 2 Remove the four screws and the cover as described in Section 6 1 Figure 14b 3 Remove the detector head by turning it counter...