USER INTERFACE CC50 SECTION / STADIUM SECTION (AIR CLEANER)
To access the Stadium hood page, simply use the navigation buttons from the main or secondary
page. On this page, you can see the filter status and differential pressure in real time.
The differential pressure is measured to determine filter clogging. When it reaches the pre-alarm
threshold, a notice is displayed to give users enough time to change the filters before reaching the
maximum clogging allowed. When maximum clogging is reached, the system shuts down
completely and displays another message.
If a filter(s) is removed, the system will detect it and shut down immediately.
If a variable speed or 2 speed system is used, 2 pressure settings must be
entered.
In a variable speed system, the pressure setting will be between the "Low"
and "High" settings (0%=Low, 100%=High) depending on cooking
activity.
In a 2-speed system, the setting used varies according to the speed
schedule. When the schedule is in high speed, the "High" setting is used,
and the "Low" setting is used the rest of the time.
When a single speed system is used, only the "Low" setting is used.