LOCATION 182: FORMAT OVER-RIDE LOCATION 

The number selected in this location will select the format options as follows: 

 

VALUE 

 

DESCRIPTION 

 

 
Add for extended reporting 

 

 
Add for hex digits allowed 

 

 
Add for 20PPS 

 

 
Add for 10PPS 

 
LOCATION 183: FORMAT OVER-RIDE LOCATION 

The number selected in this location will select the format options as follows: 

 

VALUE 

 

DESCRIPTION 

 

 
Add for 1800hz transmit 

 

 
Add for 2300hz handshake 

 

 
Add for single round parity 

 

 
Add for 2 digit event code

 

 
LOCATIONS 184-185: RESERVED LOCATIONS 
      
LOCATIONS 186-191: ASSIGNING SPECIAL CHARACTERISTICS FOR ZONES 1-6  

Locations 186-191 are used to assign individual characteristics for each of zones 1-6. These locations can be used to 
enable or disable the chime feature, restore reporting, bypass feature and fast loop response for each of the individual 
zones 1-6. To enable the features, enter a binary number according to the following chart: 

 

 

VALUE 

 

SPECIAL CHARACTERISTICS 

 

 
Fast loop response time (see location 180) 

 

 
Bypass Capability 

 

 
Zone Restoral Reporting 

 

 
Chime enable

 

 
LOCATION 192 - 193: RESERVED 
 
LOCATION 194: TELEPHONE LINE FAULT MONITOR 

A "1" in this location will activate the siren, a "2" will activate the keypad sounder, and a "3" will activate both any time a 
phone line fault is detected. A "9" will activate the siren, a "10" will activate the keypad sounder, and an "11" will activate 
both, if a line fault is detected only while the system is armed. If A10" or A11" is selected, Keypad Sounder will sound 
when system is disarmed.  The green "Ready" LED will flash upon detection of a phone line fault if this feature is 
selected. Factory default is "0" (disabled). 

 
LOCATION 195: TELEPHONE LINE FAULT DELAY 

Location 195 is used to program a delay of sounder activation after a phone line fault has been detected. Programmable 
in 10 second increments, a "1" through "15" will cause a delay of 10 to 150 seconds. If a "0" is programmed in this 
location the activation will be instant. If a "6" is programmed in this location the activation will be delayed 60 seconds.  

 
LOCATION 196: ANSWERING MACHINE DEFEAT 

Location 196 contains the answering machine defeat. To defeat an answering machine, two telephone calls must be 
made to the premises. On the first call, let the phone ring the same number of times (or less) as the number 
programmed in this location (maximum 3) and disconnect. The control panel will detect these rings and start a 45-
second timer, during which, the control panel will answer the next call on the first ring. This location will override location 
280 if it contains something other than a "0" (factory default).  

 

Summary of Contents for Ranger 8600E

Page 1: ...o Program the Ranger 8600E 7 Keypad Programming Examples 8 Programming Phone Numbers Formats 9 Communicator Format Selection Guide 10 Optional Programming Instructions 10 27 Download Programming Instr...

Page 2: ...r 8600E functions After installation of the security system complete the information on page 1 of the users manual and explain the system operation to all security system owners operators Standard Par...

Page 3: ...e programmed for dual and or split reporting DYNAMIC BATTERY TEST When enabled in location 203 the 8600E can be programmed to perform a dynamic battery test for a selected duration at 6 00 AM ENTRY GU...

Page 4: ...iration program a 4 For a bell test at closing kissoff program an 8 The 8600E allows downloading of custom information to 9050 LCD keypads The 8600E has a Fire Alarm Verification feature which can be...

Page 5: ...5 Terminal Drawing Special Notes...

Page 6: ...d be 15 watt at 8 or 16 ohm or 30 40 watt at 4 8 or 16 ohms If siren driver disable is selected in location 132 output becomes voltage output 12VDC 1 Amp maximum load 16 17 Smoke detector power 12VDC...

Page 7: ...9 you would determine that the data in location 000 is 9 2 If the data in location 000 is 6 the LED for zone 2 2 and zone 3 4 would be added 2 4 6 indicating the data in that location to be 6 3 If no...

Page 8: ...8...

Page 9: ...s a local only control LOCATION 053 DISABLING THE SECONDARY TELEPHONE NUMBER AS A BACKUP Location 053 is used to disable the secondary phone number as a backup This feature can be used with split repo...

Page 10: ...G THE MASTER ARM DISARM CODE Locations 000 003 contain master arm disarm code user number 1 Location 000 contains the first digit of the code location 003 contains the fourth digit of the code THE COD...

Page 11: ...ime of 12 minutes NOTE This location shall be programmed for a minimum of 4 minutes on UL Listed systems LOCATIONS 078 083 PROGRAMMING THE ZONE TYPES Locations 078 through 083 contain a number identif...

Page 12: ...keys are pressed simultaneously on the keypad The desired Keypad panic code is programmed in locations 092 093 If both locations are 0 the Keypad panic double keypress is disabled Location 092 contai...

Page 13: ...h time zone 1 creates an alarm Location 104 contains the standard digit and location 105 contains the extended digit When using 4 2 format the number programmed in location 104 is sent as the ones dig...

Page 14: ...format is selected the restorals will be reported by zone If a restoral code is programmed and an extended format is not selected a restoral code will be sent when all of the previously reported cond...

Page 15: ...15...

Page 16: ...for the appropriate phone number s before ending the notification process If this location contains an 8 the communicator will make eight attempts to the first number and then eight attempts to a seco...

Page 17: ...sarm code VALUE DESCRIPTION 1 Activation by pressing 1 and 7 keys simultaneously 2 Momentary activation at arming 4 Momentary at end of exit delay 8 Momentary at kiss off ringback LOCATION 143 SMOKE P...

Page 18: ...ollowing chart and program the sum in this location For example to reverse outputs 2 and 3 program a 6 2 4 6 in location 149 VALUE DESCRIPTION 1 Invert auxiliary 1 output 2 Invert auxiliary 2 output 4...

Page 19: ...the 24 hour time is 17 25 so this location should contain a 1 which is the current hour tens digit If the current time is 9 36 AM the 24 hour time is 09 36 so this location should contain a 0 LOCATION...

Page 20: ...s 086 087 NOTE FOR U L GRADE A INSTALLATIONS THIS FEATURE SHALL BE DISABLED LOCATION 168 171 PROGRAMMING THE SEED CODE FOR ROTATING MAINTENANCE CODES Locations 168 171 contain the complex or seed code...

Page 21: ...G PROGRAMMING TAMPER DOWNLOAD COMPLETE AND AUTOTEST TO REPORT TO THE SECONDARY PHONE NUMBER The 8600E is capable of sending certain reports to the secondary telephone number This feature known as spli...

Page 22: ...r of 10 second increments in the secondary entry delay This delay can be programmed from 10 to 150 seconds 1 10 sec thru 15 150 sec NOTE ACCORDING TO SEC 26 OF U L 1023 THE SECONDARY ENTRY TIME SHALL...

Page 23: ...keypad sounder and a 3 will activate both any time a phone line fault is detected A 9 will activate the siren a 10 will activate the keypad sounder and an 11 will activate both if a line fault is det...

Page 24: ...tery testing during each 24 hour period The red Power LED will flash if the battery fails the dynamic test Factory default is 0 disabled NOTE The clock must be set locations 153 161 for dynamic batter...

Page 25: ...ocation 207 controls the use of the callback telephone number The callback number must be programmed in the download section for this location to have an effect The callback number will be used accord...

Page 26: ...34 will be used LOCATION 241 LISTEN IN TIME Location 241 is used to program Listen In time in 30 second increments Valid entries are 1 3 1 30 3 90 LOCATION 242 RESERVED LOCATION 243 ENTRY KEYPAD SOUND...

Page 27: ...ted in the instructions provided with the CADDX download software package LOCATIONS 264 279 CALL BACK TELEPHONE NUMBER The presence of a phone number in locations 264 279 will cause the control panel...

Page 28: ...Time Out 2 Minute Increments 4 8 Minutes 078 11 Zone 1 Type 3 Entry Exit 079 11 Zone 2 Type Locations 078 083 5 Int Follower 080 11 Zone 3 Type DATA TYPE DATA TYPE 6 Instant 081 11 Zone 4 Type 1 Day Z...

Page 29: ...utput 2 1 Fire Alarm 147 17 Auxiliary Output 3 2 Panic Duress 148 17 Auxiliary Output 4 3 Armed State 149 18 Inverting The Auxiliary Outputs 0 High Going Low 150 18 Delay Ac Power Loss Report 3 6 Minu...

Page 30: ...ng Hour Tens Digit 2 199 24 Time For Automatic Arming Hour Ones Digit 0 200 24 Time For Automatic Arming Minute Tens Digit 0 201 24 Time For Automatic Arming Minute Ones Digit 0 202 24 Automatic Armin...

Page 31: ...ith the National Electrical Code ANSI and NFPA standards When the built in digital communicator is utilized in conjunction with a U L installation it must report at a minimum a burglary zone a fire zo...

Page 32: ...ent Code SIA Code Description 1 FA Fire Alarm 2 PA Panic alarm 3 BA Burglary Alarm 4 GA Gas Alarm 5 KA Heat Alarm 6 WA Water Alarm 7 QA Emergency Alarm 8 SA Sprinkler Alarm 9 UA Untyped Alarm 10 HA Ho...

Page 33: ...ption 0 122 Silent Panic for Loc 93 only 1 110 Fire Alarm 2 120 Panic alarm 3 130 Burglary Alarm 4 131 Perimeter Alarm 5 132 Interior Alarm 6 133 24 hour Burglary 7 134 Entry Alarm 8 135 Day Night Ala...

Page 34: ...rect the situation The customer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES The telephone com...

Page 35: ...G IF ANY DEFECT APPEARS DURING THE WARRANTY PERIOD RETURN IT TO CADDX POSTAGE PREPAID THE UNIT WILL BE REPAIRED AND RETURNED FOR THE REMAINING 36 MONTHS OF WARRANTY THE UNIT WILL BE REPAIRED FOR A FEE...

Reviews: