Connecting the CSX400-DC to the Power Source
Th CSX400-DC requires either a 48 Vdc or 60 Vdc (48/60 Vdc), 3.5 A (maximum), external power
source supplied by three 18 AWG (American Wire Gauge) copper wires. These wires must be
terminated to the dc input power strip shown in
Figure 20
with either ring or spade terminals. The
dc power supply in the CSX400-DC has its own on/off switch and is rated at 100 watts. To connect
the CSX400-DC to a 48/60 Vdc power source, face the back panel, then refer to
Figure 20
and
proceed as follows:
ONLY QUALIFIED PERSONEL SHOULD PERFORM THESE INSTALLATION
PROCEDURES.
TO REDUCE THE RISK OF ELECTRIC SHOCK OR ENERGY HAZARDS:
•
CONNECT TO A RELIABLY GROUNDED 48/60 VDC SELV SOURCE.
•
ENSURE THE BRANCH CIRCUIT OVERCURRENT PROTECTION IS
RATED AT A MIMINUM OF 10 A.
•
USE 18 AWG SOLID COPPER CONDUCTORS ONLY.
•
ENSURE THAT A READILY ACCESSIBLE DISCONNECT DEVICE THAT IS
SUITABLY APPROVED AND RATED, IS INCORPORATED IN THE FIELD
WIRING.
TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN ACCORDANCE WITH
THE NEC OR THE AUTHORITY HAVING JURISDICTION.