QT601-2 Quantec Controller

Installation & Programming Manual • Approved Document No. DNU6012001 Rev 5 • Page 24 of 42

2.13   Setting Up HTM08-03 Mode

This  function  allows  Quantec's  HTM08-03  function  to  be
enabled  or  disabled.  On  selecting  the  'HTM08-03  Mode'
prompt, one of the following options will appear:

Use  the  scroll  keys  to  select  the  required  option  and  press
Accept.  When  Enabled,  the  Controller  adheres  to  certain
aspects of the HTM08-03 standard and the following changes
occur:

1. Auto Night Mode is disabled.
2. Day/Night Mode cannot be entered using the Controller's
front  panel  menus.  Instead,  you  must  use  a  single  remote
Day/Night Mode Switch (a QT611 multi-purpose programmable
device configured as a Day/Night Mode Switch).
3. The Controller's internal sounder is disabled for call type
signalling.

2.14   Setting Up Surveyor Mode

This function allows Quantec's Surveyor Mode function to be
enabled  or  disabled.  On  selecting  the  'Surveyor  Mode'
prompt, the following two options are available:

This mode is used in conjunction with Quantec's 'Surveyor'
Data  Management  Software  package.  When  enabled,  the
Controller's logging output is set to "output on every event"
and cannot be changed and the "printer fault" message on
the  panel  is  suppressed  when  the  PC  is  turned  off  or
disconnected from the panel.

2.15   Display IDs

On  selecting  the  'Display  IDs'  prompt,  the  following  two
options are available:

This function, if set to ‘Enabled’, sends Caller ID details to the
Quantec Displays when a call is presented on the system with
the information available. If disabled, this information is not
presented  on  the  Quantec  Displays.  This  function  may  be
required  for  security  reasons.  Caller  ID  information  is  still
presented on the log, if enabled.

2.16   Auto Reset

This function is used on a system with just a pager connected
and no Displays, or addressable overdoor lights / addressable
sounders. Calls are paged but automatically reset after the
assigned time.

On selecting the 'Auto Reset' prompt, the following options
are available:

Auto Reset can be either Enabled or Disabled. The Auto Reset
Time  can  be  changed  between  10  to  60  seconds  (at  10  sec
intervals).

2.17   CF in Day Mode

On selecting the 'CF in Day Mode' prompt, the following two
options are available:

Call Follow (CF) Day functionality can be enabled / disabled
using this menu option.

CF sounder in a call point, which is in the PRESENCE state, is
sounded when the panel is in Day mode. The call has to be
present on a call point in the same call point Area.

When the panel is in Night mode, any call on the system is
sounded on a call point (in PRESENCE state), in otherwords
globally.

Set HTM08-03
Mode: Enabled

Set HTM08-03
Mode: Disabled

Set Surveyor
Mode: Enabled

Set Surveyor
Mode: Disabled

Display IDs
IDs: Enabled

Display IDs
IDs: Disabled

Auto Reset Mode

Auto Reset Time

CF in Day Mode
Mode: Enabled

CF in Day Mode
Mode: Disabled

Summary of Contents for QT601-2

Page 1: ...QT601 2 QUANTEC CONTROLLER installation and programming manual Approved Document No DNU6012001 Rev 5...

Page 2: ...s 28 Appendix 4 Auxiliary Outputs 28 Appendix 5 Quantec Paging Functionality 29 Appendix 6 Wiring for Addressable Call Points Ceiling Receivers 30 31 Appendix 7 Pre Commissioning Instructions 32 34 Ap...

Page 3: ...the system as a whole The manufacturer s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice E OE Whe...

Page 4: ...infrared call points ceiling receivers and radio receivers Ideal for use in individual bedrooms or communal areas such as lounges where they eliminate the need for long and potentially hazardous tail...

Page 5: ...ing devices 10 17 are assigned as members of one Area Area A and all Displays in West Wing devices 2 and 3 are assigned as members of one Group Group 1 A similar scenario applies to the East Wing the...

Page 6: ...TABLE Call Point AREA Display GROUP Addressable Overdoor Light ZONE Max no of Addressable Devices 255 Max no of Areas 26 Max no of Groups 32 Max no of Zones 64 D Display Z Addressable Overdoor Light o...

Page 7: ...Zonal Routing Tables are located at the back of this document Quantec ZONAL ROUTING TABLE max 8 Areas Devices per equation Example Requirement 4 Although standard patient and HELP REQUIRED calls shoul...

Page 8: ...needs to be given to how they will interact until system programming Slave devices such as slave ceiling pulls slave overdoor lights and slave infrared ceiling receivers connect to Quantec via a mast...

Page 9: ...der 3 3 2 2 3 If slave overdoor lights are fitted in corridors good practice is to loop the network in and out of the overdoor lights and then spur off into the relevant addressable call point inside...

Page 10: ...to each network splitter General Purpose Wiring Instructions With Quantec a limiting factor is voltage drop which should be limited to 5 volts worse case As call points and overdoor lights take differ...

Page 11: ...Lights are not used Spine Length Calculator Use the Spine Length Calculator below to work out the maximum spine cable lengths taking into account the number and type of devices connected to any networ...

Page 12: ...pillars taking care not to damage any of the components The Controller s lid and base PCBs can now be removed to prevent accidental damage Note The base PCBs are static sensitive and relevant anti sta...

Page 13: ...llows the installer to power the system without connecting the mains supply For this to work two fully charged 12 V VRLA batteries should be connected in series as shown below always ensure correct po...

Page 14: ...s site specific data PCB retaining screw must be secured tightly before operation Lid Base connecting cable connects to PL1 on Front Panel Display and Switch PCB VR1 Volume Pot turn to increase or dec...

Page 15: ...that a particular device is programmed as anticipated A handy way of doing this is to program a Display and then press the A button which will display its ID number Whilst the autoassign function is a...

Page 16: ...2 6 2 7 2 8 2 9 2 10 2 11 2 12 2 13 2 14 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 7 1 8 2 15 2 16 2 17 1 9 1 10 4 1 4 2 4 3 4 4 4 7 4 5 4 6 Pager Mode Pager Level DECT Protocol Auto Reset Mode Auto Reset Time Pr...

Page 17: ...V Room EW01 When the final character has been accepted the Assign New Device prompt reappears Note Exiting this option before the final character has been accepted will cancel the description change 1...

Page 18: ...it Custom Texts function described in section 1 7 On pressing the Accept button your choice will be confirmed e g By using the scroll and Accept keys four single alphanumeric characters can now be tag...

Page 19: ...1 use the scroll keys to highlight Div and press Accept This equation describes where calls from the selected Group should be diverted to if a call has not been accepted before a pre determined time...

Page 20: ...essage will appear When the sending process is complete the Controller will automatically return to the Assignment Menu The renamed custom text fields will now be available to the appropriate device n...

Page 21: ...t Code This option allows Quantec s four digit Call Reset code to be entered or changed this can be any combination of the scroll up scroll down and Accept keys On selecting the Set Call Reset prompt...

Page 22: ...ALL levels of call accepting this enables paging on RESET and ALL levels of call It should be noted that different levels of calls are not prioritised by pagers For example if a STANDARD call is trig...

Page 23: ...and its confidence LED will be lit or in the case of an addressable overdoor light or sounder its beeper will be sounding at the STANDARD call rate If the state field 0 OK the device has been found by...

Page 24: ...Display IDs prompt the following two options are available This function if set to Enabled sends Caller ID details to the Quantec Displays when a call is presented on the system with the information...

Page 25: ...Please note this function will only work if the Controller s datalogger has been programmed to print manually refer to section 2 6 and a printer is properly connected to its RS232 printing port 4 3 Se...

Page 26: ...1 Stop Bit No Parity Display Parameters Note When there are concurrent Normal calls from Call Points and Monitor Points the Monitor Point Call Rate is used Call Point Parameters Addressable Overdoor...

Page 27: ...set 1 10 9 02am Lounge 2 Attack 1 10 9 02am Lounge 2 Reset 1 10 10 15am Bedroom G F 4 Call 1 10 10 15am Bedroom G F 4 Emergency 1 10 10 18am Bedroom G F 4 Presence 1 10 10 18am Bedroom G F 4 Reset Fau...

Page 28: ...Appendix 4 Auxiliary Outputs Seven auxiliary outputs are provided at the Quantec Controller as listed below The outputs can be used for driving peripheral equipment as per the following examples Exam...

Page 29: ...r only looks for the ACK once it has sent the ENQ it doesn t respond to any other data sent to it The Message embodies the paging message itself alert tone and message checksum and is assembled as fol...

Page 30: ...NNECTOR PLK1 For optional special programming functions requires QT423A adaptor L L A C LK3 P K4 L P Short to give the QT302RX an ID when in assignment mode once assigned these pins can be used to mak...

Page 31: ...t Max 3 slave call points or ceiling pulls any mix connected in parallel per master call point QT423 CONFIG CONNECTOR PLK1 For optional special programming functions requires QT423A adaptor QT607 CEIL...

Page 32: ...fitted should be in place checked certified correct Checking the Spine Wiring Power up the Quantec Controller A number of messages will flash quickly on the Controller s LCD display before the words Q...

Page 33: ...ently is backlit and shows the unassigned message This means that the display has been installed correctly If the display shows the time it is assigned and should be reset using the reset ID pins see...

Page 34: ...belled Yes No SIGNED _______________________________________ DATE ____________________________________________ CONTRACTORS NAME ________________________________________________________________________...

Page 35: ...ce voltage drop No of limbs per splitter 6 Max cable length per limb 60 m Max no of addressable devices per limb 15 Max no of addressable devices per system 255 Network voltage 24 V nominal Network ma...

Page 36: ...ation Programming Manual Approved Document No DNU6012001 Rev 5 Page 36 of 42 DEVICE Call Point AREA Display GROUP Addressable Overdoor Light ZONE PLACE DESCRIPTION Number Type Name Number Quantec Devi...

Page 37: ...Installation Programming Manual Approved Document No DNU6012001 Rev 5 Page 37 of 42 DEVICE Call Point AREA Display GROUP Addressable Overdoor Light ZONE PLACE DESCRIPTION Number Type Name Number Quant...

Page 38: ...Installation Programming Manual Approved Document No DNU6012001 Rev 5 Page 38 of 42 DEVICE Call Point AREA Display GROUP Addressable Overdoor Light ZONE PLACE DESCRIPTION Number Type Name Number Quant...

Page 39: ...tec Controller Installation Programming Manual Approved Document No DNU6012001 Rev 5 Page 39 of 42 Quantec Group Routing Table max 8 Areas Groups per equation GROUP PRIMARY AREAS NIGHT AREAS BEEP DIVE...

Page 40: ...01 2 Quantec Controller Quantec Zonal Routing Table max 8 Areas Devices per equation ZONE AREA EQUATION DEVICE EQUATION Installation Programming Manual Approved Document No DNU6012001 Rev 5 Page 40 of...

Page 41: ...R No Limb Device ID Numbers Length 1 2 Location 3 4 5 6 QUANTEC CONTROLLER NETWORK SPLITTER No Limb Device ID Numbers Length 1 2 Location 3 4 5 6 NETWORK SPLITTER No Limb Device ID Numbers Length 1 2...

Page 42: ...Device Replace Device Setup Group Setup Zone Edit Cust Texts Send Cust Texts Setup Divert Exit Menu ACCESS LEVEL 1 System Setup Set Assignment New Device Assignment Menu SystemSetupMenu Double Addres...

Reviews: