![C-TEC QT601-2 Installation And Programming Manual Download Page 16](http://html1.mh-extra.com/html/c-tec/qt601-2/qt601-2_installation-and-programming-manual_3100300016.webp)
QT601-2 Quantec Controller
Overview of Access Levels
Installation & Programming Manual • Approved Document No. DNU6012001 Rev 5 • Page 16 of 42
ACCESS LEVEL 2
or as programmed
}
A
Set Day/Night
Output Log
Set Date
Set Time
Network Reset
ACCESS LEVEL 3
Program Menu
Set Time Outs
Set AL2 Code
Set AL3 Code
Set Attack Reset
Set Call Reset
Setup Logger
Emergency G/L
Attack G/L
Paging
Auto Night Mode
Monitor Point
Display Device
Print All
Print Devices
Print Groups
Print Zones
AutoScan
Existing Device
Replace Device
Setup Group
Setup Zone
Edit Cust Texts
Send Cust Texts
Setup Divert
Exit Menu
ACCESS LEVEL 1
System Setup
Set Assignment
New Device
Assignment Menu
System Setup Menu
or as programmed
}
Double Address
1
2
3
4
E
V
Quantec Controller keys
= ACCEPT
= SCROLL UP
= SCROLL DOWN
= ESCAPE
V
=
1
=
2
=
3
=
4
Set Day/Night
Output Log
Set Date
Set Time
Network Reset
HTM08-03 Mode
Surveyor Mode
Edit ID Texts
Send ID Texts
Display IDs
Auto Reset
CF in Day Mode
Edit Sys Name
Send Sys Name
Clean Start?
V
A
A
A
2 2 2 2
3 3 3 3
4.1
4.2
4.3
4.4
4.7
3.1
3.2
3.3
3.4
3.5
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.7
1.8
2.15
2.16
2.17
1.9
1.10
4.1
4.2
4.3
4.4
4.7
4.5
4.6
Pager Mode
Pager Level
DECT Protocol
Auto Reset Mode
Auto Reset Time
Program Menu
2.9
2.9
2.9
2.16
2.16
Three ‘access levels’ are available at the Quantec Controller:
• G
eneral User (Access Level 1)
•
Authorised User (Access Level 2)
•
Engineer (Access Level 3).
All programming functions are located in Access Level 3 and
can be accessed by inputing a four digit code at the Controller
(default code = 3 3 3 3).
Note
: The Controller will automatically
exit Access Level 3 after 1 hour without a key press.
Entry to Access Level 2 requires the input of a different code
(default code = 2 2 2 2).
Note
: The Controller will automatically
exit Access Level 2 after 5 minutes without a key press.
Entry to Access Level 1 does not require an access code.
The menu options available are shown on the menu tree
(right) and are described in detail in this section. Refer to the
subsection number below each menu option for detailed
information on that feature.
Note
: The 'NVM' link (located on the Main Control PCB) must
be fitted during the programming process in Access Level 3.
This unlocks the non-volatile memory on the Controller and
allows site specific data to be modified.