EP203 AUTOMATIC EXTINGUISHER PANEL
Page 30 of 45 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Approved Document No. DFU0002032 Rev 4
Ex t . O /P E O L s
The extinguishant output end-of-line sub-menu sets the number of extinguisher System
Line Terminators to either 1 or 2.
1.
From the Commissioning menu, select Ext. O/P EOLs.
2.
Select the required number of terminations using the Scroll (up) and Scroll (down)
buttons.
3.
Press the Accept key to confirm the changes. The Commissioning menu is displayed.
Mode Except i o n s
This sub-menu sets the default setting of mode when the mode input is in fault and/or
disabled.
1.
From the Commissioning menu, select Mode Exceptions.
2.
Select either default Mode on Fault, or default Mode on Disable using the Scroll (up)
and Scroll (down) buttons.
3.
Select either Manual Only, or Auto/Manual Mode using the Scroll (up) and Scroll
(down) buttons.
4.
Press the Accept key to confirm the mode changes.
5.
Press the Escape key. The Commissioning menu is displayed.
Ear t h Fa ul t
This sub-menu enables/disables the earth fault circuitry.
1.
From the Commissioning menu, select Earth Fault.
2.
Select either the enabled, or disabled option using the Scroll (up) and Scroll (down)
buttons.
3.
Press the Accept button to confirm the changes. The Commissioning menu is displayed.
Man Re l M o de
The manual release mode sub-menu selects either delayed, or immediate release of
extinguishant.
1.
From the Commissioning menu, select Man Rel Mode.
2.
Select either the delayed, or immediate option using the Scroll (up) and Scroll (down)
buttons.
3.
Press the Accept button to confirm the changes. The Commissioning menu is
displayed.
Zone T r i gge r
This sub-menu enables a short-circuit condition on the three detection zones.
1.
From the Commissioning menu, select Zone Trigger.
2.
Select the detection zone using the Scroll (up) and Scroll (down) buttons and press
the Accept button.
3.
Select either the S/C, or Normal option using the Scroll (up) and Scroll (down) buttons.
4.
Press the Accept button to confirm the changes. The Commissioning menu is displayed.