I g n i t i ng Ac t ua t o r (Me t r o n ™ ) W i r i n g
The extinguishant output is capable of supplying up to 3 amps for the maximum
duration (50 milliseconds) to an igniting actuator.
The total series resistance of the actuator(s) and wiring should NOT exceed 7 ohms.
Figure 9 : Typical Igniting Actuator Circuit Wiring
W i r i ng f o r o ne act ua t o r :
W i r i n g f o r m u l t i p le ac t ua t o r s :