![C-TEC EP203 Installation And Maintenance Manual Download Page 22](http://html1.mh-extra.com/html/c-tec/ep203/ep203_installation-and-maintenance-manual_3100392022.webp)
EP203 AUTOMATIC EXTINGUISHER PANEL
Page 22 of 45 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Approved Document No. DFU0002032 Rev 4
PROGRAMMING THE EP203 PANEL
Three levels of control are available on the EP203 panel: General User (Access Level 1),
Authorised User (Access Level 2) and Engineer (Access Level 3) as detailed below:
Note : For detailed information on how to use the general and authorised user controls,
refer to the EP203 panel User Manual/Log Book (Approved Document No. DFU0002031).
G en e r al U s e r Controls (Acces s L ev el 1 )
The functions that can be performed in Access Level 1 are:
•
Manually activate the extinguisher release
•
Mute the internal sounder.
Also, by pressing the ‘menu’ button, the LCD unit displays the following Access Level 1 menu:
Authoris ed Us e r Controls (Acce s s Lev el 2)
The functions that can be performed in Access Level 2, by turning the panel-mounted
keyswitch to the ‘accessed’ position, are:
•
Manually activate the extinguisher release
•
Mute the internal sounder
•
Silence the alarm sounders
•
Resound the alarm sounders
•
Reset an alarm condition.
Also, the LCD unit displays the following Access Level 2 menu:
Display Faults
Display Dis/mnt
Zones in Test
Lamp Test
Alarm Counter
Set Time/Date
Event Log
Disp Contrast
Disablements
ENGINEERING
Display Faults
Display Dis/mnt
Zones in Test
Lamp Test
Alarm Counter
www.acornfiresecurity.com
www.acornfiresecurity.com