EP203 AUTOMATIC EXTINGUISHER PANEL
Page 28 of 45 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Approved Document No. DFU0002032 Rev 4
Commissioning
Zone Se lect i o n
This sub-menu programs the zone combination that starts the extinguishant release
sequence.
1.
From the Commissioning menu, select Zone Selection.
2.
Highlight the required zone selection using the Scroll (up) and Scroll (down) buttons.
The options are listed below:
NONE
Z1 & Z2, Z2 & Z3, Z1 & Z3, Z1 & Z2 & Z3
Z1 OR Z2, Z2 OR Z3, Z1 OR Z3, Z1 OR Z2 OR Z3
(Z1 & Z2) OR (Z1 & Z3), (Z1 & Z3) OR (Z2 & Z3), (Z2 & Z1) OR (Z2 & Z3)
(Z1 & Z2) OR Z3, (Z1 & Z3) OR Z2, (Z2 & Z3) OR Z1
ANY PAIR.
3.
Press the Accept button to confirm the zone selection. The Commissioning menu is
displayed.
Ex t . De lay
The extinguishant delay sub-menu sets the countdown duration before the
extinguishant is released.
1.
From the Commissioning menu, select Ext. Delay.
2.
Select the required duration using the Scroll (up) and Scroll (down) buttons. This is
adjustable between 0-60 seconds (in 1 second steps).
3.
Press the Accept button to confirm the changes. The Commissioning menu is
displayed.
Ex t . D ura t i o n
The extinguishant duration sub-menu sets the duration of the firing signal to the
extinguishant output, typically 2 secs.
Note : Keep the extinguishant duration to a minimum in order to minimize current
consumption.
1.
From the Commissioning menu, select Ext. Duration.
2.
Select the required duration using the Scroll (up) and Scroll (down) buttons. This is
adjustable between 1-300 seconds (in 1 second steps).
3.
Press the Accept button to confirm the changes. The Commissioning menu is
displayed.
F l ood i ng T i me
This sub-menu sets the flooding time.
1.
From the Commissioning menu, select Flooding Time.
2.
Select the required duration using the Scroll (up) and Scroll (down) buttons. This is
adjustable between 60-1740 seconds (in 1 second steps).
3.
Press the Accept button to confirm the changes. The Commissioning menu is
displayed.