EP203 AUTOMATIC EXTINGUISHER PANEL
Page 26 of 45 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Approved Document No. DFU0002032 Rev 4
Dis ablem ent s
The Disablements menu allows the temporary disabling, or enabling of the
extinguishant system, detection zones, sounders, monitored inputs, relays and RSUs. The
Disablements menu is available at both Access Levels 2 and 3. Any active disablements
are displayed at the EP203 panel by the General Disablement and relevant disablement
yellow LEDs lit steady.
Note : It is recommended all disablements are immediately enabled when no longer
required as they can have a major effect on how the system works.
D i sa ble Ex t i n g
This sub-menu allows the disabling/enabling of the extinguishant system.
1.
From the Disablements menu, select the Disable Exting sub-menu.
2.
Press the Accept button to disable/enable the extinguishant system.
3.
Press the Escape button to return to the Disablements menu.
Note : ‘Exting System Disabled’ will also be displayed at any RSUs connected on the
system.
D i sa ble Zone
This sub-menu allows the disabling/enabling of one, or more of the panel’s three
detection zones. Disabled zones do not report fire, or fault conditions.
1.
From the Disablements menu, select the Disable Zone sub-menu.
2.
Select the detection zone(s) to be disabled/enabled using the Scroll (up) and Scroll
(down) buttons.
3.
Press the Accept button to disable/enable a selected zone.
4.
Press the Escape button to return to the Disablements menu.
D i sa ble S ou nde r
This sub-menu allows the disabling/enabling of the fire sounders from sounding in a fire
condition.
1.
From the Disablements menu, select Disable Sounder.
2.
Press the Accept button to disable/enable the sounder circuit.
3.
Press the Escape button to return to the Disablements menu.
D i sa ble S nd r De l
The sounder delay sub-menu allows the disabling/enabling of a fire sounder delay in a
fire condition.
1.
From the Disablements menu, select Disable SndrDel.
2.
Press the Accept button to disable/enable the delay on the sounder circuit.
3.
Press the Escape button to return to the Disablements menu.