Check battery quality.
To check the battery quality, the device periodically connects the load and monitors the voltage drop. If the voltage
drop under the load exceeds 2 V, the event
E309
-
Faulty battery
is generated.
If UPS is connected
Figure 61: “Miscellaneous” tab, “Backup power supply” section, ”UPS” is selected for “Type of backup power
supply”
If the UPS is selected as a backup power source, enabling of the additional parameters (protection against deep
discharge and battery quality control) is not available.
5.7.4
Arm and disarm
In this section, it is possible to specify various parameters that will affect the process of arming or disarming.
Figure 62: “Miscellaneous” tab, “Arm and disarm” section
Disable arming when triggering the alarm in zones with exit delay
By default, the alarm in zones with exit delay is ignored at the time of arming. This is done so that the user can
arm the site and close the entrance door behind him/her without hurry. But, if you want to be sure that all alarm
zones are normal at the time of arming, it is possible to enable alarm monitoring in zones with exit delay. To do
this, check the
Disable arming when triggering the alarm in zones with exit delay
box.
Disable arming when no main power supply (AC) is available
If this parameter is set, the device cannot be armed if it is running on a backup power supply and the main one is
not available.
Disable arming when no IP communication with the Security Center is available
If this parameter is set, the device cannot be armed if there is no GPRS or Ethernet communication.
Enable remote arm/disarm from the Security Center
This parameter allows to remotely control the protection state from the mobile application and the repeater.
Enable duress codes
The code of forced disarming is a code that differs from the user code by one unit plus or minus. For example, if
the user code is “1234”, then the forced disarming codes will be “1233” and “1235”. At the same time:
∙
if the user code ends with “0”, then the forced disarming code will be only one – one more. For example, if
the user code is “5840”, then the forced disarming code will be only “5841”.
65