6 Electrical Connection
Shenzhen BYD Electronic Co., LTD
30
HVS&HVM Operating Manual
6.6.
Connecting the Network Cables
•
Shielding: Yes
•
UV-resistant for outdoor use
•
Straight- through wired cables
•
Maximum cable length: 20 m.
Procedure:
1.
Take off the nut of the cable gland a.
2.
Take the cable support sleeve inside of the cable gland.
3.
Take out the plug and get the network cable inside of the cable support sleeve.
4.
Lead the network cable through cable gland a.
5.
Plug the cable to the corresponding RJ45 port.
DANGER
Danger to life due to electric shoc
k
in case of overvoltages and if surge protection is missing
O
vervoltages (e. g. in the event of a flash of lightning) can be further conducted into the building and to
other connected devices in the same net
w
or
k
via the net
w
or
k
cables or other data cables if there is no
surge protection. Touching live parts and cables results in death or lethal injuries due to electric shoc
k
.
•
E
nsure that all devices in the same net
w
or
k
and the battery are integrated into the
e
x
isting
surge
protection.
•
W
hen laying the net
w
or
k
cables or other data cables outdoors, it must be ensured
that a suitable
surge protection device is provided at the transition point of the cable
from the
system
or the
inverter
outdoors to the inside of a building.
The connection to
the
Internet is not mandatory, but recommended.
Additionally required material (not included in the scope of delivery):
•
One
network cable
(Cat5, Cat5e or higher)
Data
cable requirements:
The cable length and quality affect the quality of the signal. Observe the following cable
requirements.
•
Cable category: Cat5, Cat5e or higher
•
Plug type:
Metal Shielded
RJ45 of Cat5, Cat5e or higher