5. 

ADDING SALT TO THE POOL:

Before adding salt to the pool, check that the each of the water equilibrium parameters are within range:

• 

pH, ideally between 7.2 and 7.4 with EES

• 

Calcium hardness (water hardness = concentration of dissolved calcium), between 200 and 400 ppm

• 

T.A. (total alkalinity), between 80 and 120 ppm

Use these parameters to ensure that the water is correctly balanced (Taylor balance or Langelier index – 

see appendix 1)

 

!

IMPORTANT

 If the pool was treated with PHMB in the past, eliminate all of this disinfectant before 

starting the electrolyser.

 

!

Only use pool grade salt as stipulated in the standard EN 16-401. No other types of salt should 

be used.

If the pool has not just been entirely refilled,  measure the salt concentration with a suitable device because 

it may contain a little salt if the water was treated with Chlorine before the electrolyser was installed.  
Calculate the weight of salt to be dissolved to achieve a concentration of 3.5 g/litre (3500 ppm) in the pool 

water. This will depend on the volume of water in the pool (do not forget the buffer tank if the pool has an 

overflow feature), and the initial salt concentration measured beforehand.

USE THE FOLLOWING TABLE:

0

500

1000

1500

2000

2500

3000

3500

4500

10

40

35

30

25

20

15

10

5

0

20

80

70

60

50

40

30

20

10

0

30

120

105

90

75

60

45

30

15

0

40

160

140

120

100

80

60

40

20

0

50

200

175

150

125

100

75

50

25

0

60

240

210

180

150

120

90

60

30

0

70

280

245

210

175

140

105

70

35

0

80

320

280

240

200

160

120

80

40

0

90

360

315

270

225

180

135

90

45

0

100

400

350

300

250

200

150

100

50

0

110

440

385

330

275

220

165

110

55

0

120

480

420

360

300

240

180

120

60

0

130

520

455

390

325

260

195

130

65

0

140

560

490

420

350

280

210

140

70

0

150

600

525

450

375

300

225

150

75

0

Volume (in m3) of water

Initial salt concentration (ppm) in the pool

Quantity (in kg) of salt to be added to the pool

 EXAMPLE:

A pool containing 100 m3 of water with an initial salt concentration of 1000 ppm (1g/litre) -> add 300 kg of 

salt to obtain a final salt concentration of  3.5 g/litre.

The quantity of salt calculated should be added as follows:

• 

Spread the salt evenly over the entire surface of the pool: the salt pellets settle on the floor of the pool;

• 

Start the filtration pump and let it run continuously until the salt is totally dissolved (approximately 8 hours);

 

!

IMPORTANT 

Do not turn the electrolyser  on while the salt is dissolving.

Summary of Contents for EES

Page 1: ...9 08 Indice de r vision D Code 29650 TRAITEMENT DE L EAU 37 72 INSTALLATION AND OPERATING INSTRUCTIONS to be read carefully and kept for future reference EES ET ESS PRO Electrolysers FR PAGE 1 EN PAGE...

Page 2: ...tion 46 4 5 3 Procedure 47 4 5 4 When starting up for the first time 49 4 6 Installing the sensors 49 4 6 1 The REDOX sensor 49 4 6 2 pH sensor 50 4 7 Installing the electrical control panel 50 4 7 1...

Page 3: ...gh and low ph and redox alarms EES Pro only 63 9 8 1 pH HIGH 63 9 8 2 PH LOW 64 9 8 3 ORP HIGH 64 9 8 4 ORP LOW 64 9 9 Ph or redox sensor faults EES Pro only 64 9 10 pH Redox circuit board fault EES P...

Page 4: ...n which it is mounted These parameters will need to be measured regularly and the pH will need to be adjusted when necessary With the acid dosing pump option installed EES can inject acid to lower the...

Page 5: ...t When handling acid and during interventions on the pump or its tubing protective glasses and clothing should be worn to protect against splashes In the event of contact with the skin flush the area...

Page 6: ...EES Pro Electrical control panel 1 The panels of all models have the same outer appearance and the same dimensions Nevertheless the electrical spcifications functional specifications and the internal...

Page 7: ...nject acid into the hydraulic circuit The acid dosing pump kit includes 2 saddles 50 63mm 3 8 to 1 2 adaptor a check valve valve internal replacement tube 2 x 3m polyethylene tube foot filter and weig...

Page 8: ...remains in the cell In some configurations this will require installation of a check valve The flow sensor should be positioned such that the acid used to descale the cell will not touch it A check v...

Page 9: ...d air Pr cautions vis vis des sondes Les parties immerg es des sondes doivent toujours rester immerg es eau de piscine ou du robinet m me hors fonction ne doivent jamais tre touch es avec les doigts n...

Page 10: ...acid pump and saddle clamp 2 Chlorinator Cell 3 Tee with pH and ORP sensors 4 Flow switch Tee 4 5 2 Horizontal installation 1 Dosing acid pump and saddle clamp 2 Chlorinator Cell 3 Tee with pH and OR...

Page 11: ...re you wish to install the acid pump on the wall Check that the all components electrical wiring tubes etc reach their position Drill and attach the acid pump s clip to the wall and hang the pump on i...

Page 12: ...mm wrench Wrap the threads of the saddle clamp adapter to with Teflon tape and insert it into the saddle clamp Wrap the check valve threading with Teflon tape andinsert it into the adapter Cut the tub...

Page 13: ...ump in MANUAL mode for a few minutes Make sure the red light on the pump is energised that it is running and that acid is being sucked from the acid container and expelled through the injection tube 4...

Page 14: ...end of the sensor into the union until the end of the sensor is located in the centre of the pipe through which the water is flowing Screw the nut firmly onto the union and check that the sensor canno...

Page 15: ...5 m tres mais dans tous les cas plus de 2 m tres du plan d eau sous r serve que son c ble d alimentation soit directement reli un dispositif di rentiel r siduel d clenchant 30 mA exigences norme NF C...

Page 16: ...ory with acid dosing LN2 Live slaved to filtration Cover panel dry contact EES output is unchanged is no voltage is detected at the contact Flow switch Water T C sensor Cell pole Cell pole N Dosing pu...

Page 17: ...panel and acid dosing pump LD2 slaved live cell Nota bene to avoid electrical disturbances when the pump starts and stops the EES power cables should not be in contact with those of the filtration pu...

Page 18: ...buffer tank if the pool has an overflow feature and the initial salt concentration measured beforehand USE THE FOLLOWING TABLE 0 500 1000 1500 2000 2500 3000 3500 4500 10 40 35 30 25 20 15 10 5 0 20 8...

Page 19: ...e message OFF is displayed on the LCD screen Press the ON OFF button 7 If the flow of water past the flow sensor is adequate 5 m3 h the message ON EES or AUTO EES Pro indicating that production of Chl...

Page 20: ...he EES models only the chlorine output can be adjusted manually by the user by pressing the two arrow keys and This setting will be saved to memory for when the device is started in the future even if...

Page 21: ...nd maintain it at this temperature if the pool is not equipped with a heating system simply wait until the water naturally reaches the lowest temperature at which bathers will use the pool Next adjust...

Page 22: ...to switch to Turbo mode the word Turbo blinks at the bottom of the output scale The Turbo mode duration is set to 12 hours in the factory this setting is displayed on screen Successive presses on the...

Page 23: ...ion of Chlorine is decreased to 20 by default The value by which Chlorine production is decreased while the pool is covered may be modified by the user using the arrow keys and The new value will be s...

Page 24: ...n EES the cell must be removed from the hydraulic circuit for descaling 8 7 Punctual or periodic reduction of the ph by the acid dosing pump This function concerns EES Pro and also EES if the acid dos...

Page 25: ...f salt In the event of a low salt warning check that the electrodes are clean and check the salt concentration with a suitable tester in case of doubt A faulty temperature sensor could also cause a lo...

Page 26: ...along with other indicators if the salt concentration is too low as described previously 9 3 Flow rate too low The message NO FLOW and the icon appear indicating that there is either no flow or insuff...

Page 27: ...isplayed at the bottom of the LCD screen Cut power to the electrical control panel open the lid of the connection terminal compartment check the condition of the connector contacts the two wires comin...

Page 28: ...for the Chlorine concentration to fall and to see if the phenomenon reoccurs 9 8 4 ORP LOW ORP LOW this message is displayed when the value measured by the Redox sensor is less than 525 mV If no previ...

Page 29: ...agitate them Rinse the sensors thoroughly after degreasing After being descaled and degreased the sensors should be recalibrated see the next paragraph and the correspondence between the Redox potent...

Page 30: ...the filtration pump off ST BY mode close the valves of the by pass loop on which the tee housing the sensors is mounted place a bucket under the tee to collect any water Remove the pH and the Redox s...

Page 31: ...the tube until it is completely out Note It is advisable to flush the pump with running tap water in order to dilute any remaining acid which may have spilled from the tube Disconnect both ends of the...

Page 32: ...or 10 Hydrochloric acid into the cell Wait until the scale is completely dissolved stops frothing If scale is still present empty the cell and repeat the procedure with vinegar or acid Rinse the cell...

Page 33: ...erizing chemicals are added to the water to prevent the growth of algae andfiltration is run every day Filtration must notably be run while the ambient temperature in the plant room where the material...

Page 34: ...is less than 10 h day The salt concentration is barely within range Measure the salt concentration and if necessary adjust it so that it is between 4 5 and 5 0 g l Scale is starting to build up on th...

Page 35: ...l remove the lid covering the panel connection terminals and tighten the power cable connections The fuse protecting the main circuit board has blown Contact the after sales service for inspection and...

Page 36: ...2019 08 Indice de r vision D Code 29650 TRAITEMENT DE L EAU 72 72 S A au capital de 7 000 000 R C S Rennes B 333263846000 37...

Reviews: