EN
25
approx. 40
mm
Quartz glass tube
O-ring
6 Installation
The unit is attached vertically to the wall.
When installing the unit leave at least 1.3 m of clearance above the unit
to facilitate emitter replacement.
● Attach the switching box (3) to the wall.
●
Earth the switching box using the earthing cable supplied
(welded setscrew at the top of the unit).
● Unscrew both setscrews (7) and remove the blue
protective cap (11)
● Unscrew the tensioning screw (8).
● Push the o-ring (6) from the bag of accessories approx. 40 mm
over the top of the quartz glass tube (5).
● Insert the quartz glass tube (5) (follow the lower guide in
the radiation chamber).
● Tighten the tensioning screw (8) hand-tight (with a small gap
between the setscrew and the cover of the UV unit).
● Insert the emitter (9) carefully and connect with the plug (10)
of the blue protective cap (11). Ensure that the plug is inserted
properly.
● Attach the blue protective cap (11) and secure it with both setscrews
(7).
WARNING!
Ultraviolet Radiation!
Risk of damage to eyes and skin!
►
UV emitters may only be started in the unit
when the blue protective cap (11) is mounted
►
Never look through sensor window with unpro-
tected eyes.
►
Use your personal protective equipment - safe-
ty goggles.
7 Startup
●
Open the water supply line.
●
See UV-Control II installation and operating instructions for the re-
maining startup procedure.