7 | Settings
32 / 44
Instruction Manual PLUS Master Control R5 PLUS_EN_en
7.1.2 Settings Screen 2
HOME
OPERATIONS
TREND
SETTINGS
NEXT
Auto pump change in case of
warning
On
PREVIOUS
Auto warning acknowledgment
Off
The function “Auto pump change in case of warning” allows the PLUS Master Control
system to automatically de-prioritize vacuum pumps with active warnings to avoid the
risk of an alarm or a failure.
When the function is activated, all vacuum pumps in the system with an active warning
will be de-prioritized: the system will use these pumps only if all the other pumps are al-
ready in operation and additional pumps are required to reach the vacuum target. As
soon as a vacuum pump can be stopped by the PLUS Master Control, pumps with active
warning will be stopped first.
To activate the function:
• Switch on the “Auto pump change in case of warning” button, password required
►
.
NOTE
Auto pump change in case of warning.
If the option "Auto pump change in case of warning" is activated (
), it will have priority over the control of the vacuum pumps operating hours
by the PLUS Master Control system.
In case of active warnings on some vacuum pumps that would not be acknowledged by
users, an offset may therefore occur in the planning of the operating hours of these
pumps.
To overcome this, it is also possible to automatically acknowledge warnings directly from
the control interface of the PLUS Master Control. This option is useful if the user prior-
itizes the planning of the operating hours of the vacuum pump by the PLUS Master Con-
trol system.
After a warning appears on a vacuum pump, and as soon as it is no longer active, it will
be automatically acknowledged by the system. The pump will no longer be de-prioritized
and can be used by the PLUS Master Control according to the parameters defined by the
user in the screen “Unequal running hours between vacuum pumps” (
).