155
107774-01- 9/17
Table A3: Approximate Starting Number of Throttle Turns
Model Size
# Counter-clockwise Turns (From Fully Closed)
Natural Gas
LP Gas
135
12-1/4
9
150
10
10
180
15
14
Appendix A - (continued)
Model No.
Fuel
Approximate Derate per 1000 ft.
2001-6000 ft.
6001-7800 ft.
7801-10,100 ft.
K2WTC-135B
NG
1.2%
1.8%
2.4%
LP
1.7%
3.3%
Not Permitted
K2WTC-150B
NG
2.6%
2.9%
3.1%
LP
3.2%
3.0%
3.3%
K2WTC-180B
NG
Not Permitted
LP
NOTE: THESE DERATES ARE AT MINIMUM VENT LENGTH Max. Vent Length 135 eq. Feet (3 inch Intake/
Vent Pipe)
Table A2: K2WTC Altitudes Derates