VIII. Gas Piping
(continued)
CAUTION
Support the weight of the gas line piping independently from the boiler gas connection fitting located on the
bottom of the boiler.
If an additional regulator is used to reduce boiler inlet pressure below 1/2 psig (3.4 kPa) it must be at least 6
to 10 ft. upstream of the boiler.
It is very important that the gas line is properly purged by the gas supplier or utility company.
Figure 8.1: Gas Connection to Boiler
NOTICE
Install 1/2” ground joint union (nut side down) as shown in Figure 8.1. Failure to do so will make it difficult
or impossible to remove burner for servicing.
Model
Max. (Natural & LP)
Min. (Natural)
Min. (LP)
135-180
14.0”
2.5”
11.0”
Table 8.2: Minimum and Maximum Inlet Pressures
Summary of Contents for K2WTC
Page 81: ...81 107774 01 9 17 X Domestic Hot Water Piping continued Figure 10 1 Domestic Hot Water Piping ...
Page 88: ...88 107774 01 9 17 XI Wiring continued XI Wiring continued ...
Page 89: ...89 107774 01 9 17 Figure 11 7 Internal Wiring Connections Diagram XI Wiring continued ...
Page 100: ...100 107774 01 9 17 Lighting and Operating Instructions XII Start Up and Checkout continued ...
Page 141: ...141 107774 01 9 17 XVI Repair Parts continued ...
Page 144: ...144 107774 01 9 17 XVI Repair Parts continued ...
Page 147: ...147 107774 01 9 17 XVI Repair Parts continued ...
Page 149: ...149 107774 01 9 17 XVI Repair Parts continued ...
Page 151: ...151 107774 01 9 17 XVI Repair Parts continued 120 121 122 123 124 125 126 127 ...
Page 158: ...158 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 159: ...159 107774 01 9 17 SERVICE RECORD DATE SERVICE PERFORMED ...