64
Operation and function
14.2.3
X.LIMIT
-
Stroke limit
This function limits the (physical) stroke to specified % values (lower and upper). In doing so, the stroke
range of the limited stroke is set equal to 100 %. If the limited stroke range is left during operation, negative
actual positions or actual positions greater than 100 % are shown.
Factory setting: Lower position limit = 0 %, upper position limit = 100 %
Adjustment ranges:
Stroke limit minimum: 0 – 50 % of the entire stroke
Stroke limit maximum: 50 – 100 % of the entire stroke
The minimum distance between the upper and lower stroke limit is 50 %. Therefore if one value is entered
with a minimum distance of < 50 % the other value is adjusted automatically.
Limited
stroke
Unlimited
stroke
Physical
stroke (%)
Limited
stroke (%)
Set-point value
[mA] (
INPUT
)
Adjustment
range
in
MANU
AL
mode
Contr
ol r
ange in
A
UT
OMA
TIC mode
Figure 38:
X.LIMIT graph
english