55
Operation and function
14.1.1
DIR.CMD
-
Reversal of the effective direction of the positioner set-point
value
You can use this function to adjust the effective direction between the input signal (INPUT) and the nominal
position of the actuator.
Factory setting: OFF (ascending)
Position
Function
ON
Reversal of the effective direction of the set-point value (
DIR.CMD
)
(set-point value 20 – 4 mA corresponds to position 0 – 100 %), fall
OFF
Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position 0 – 100 %), rise
Table 27:
Effective direction
Nominal position
Input signal
(
INPUT
)
rise
fall
Figure 32:
DIR.CMD graph