29
Control and display elements
MANUAL operating status (manual LED is lit red):
Button
Function
LED
1
Press and hold
Aerate
(manually open / close the
actuator)
15)
2
Press and hold
Deaerate
(manually open / close the
actuator)
15)
1 and 2
simultane-
ously
Press longer than 2 s
(< 10 s)
Switching to AUTOMATIC ope-
rating state
Manual LED flashes at 5 Hz
(0 – 2 s)
Press longer than 10 s
(< 30 s)
Device restart
Manual LED, charact LED
and cutoff LED flash at 5 Hz
(10 – 30 s)
Press longer than 30 s
Reset device to factory setting
Manual LED, charact LED
and cutoff LED flash at 10 Hz
(> 30 s)
Table 8:
Configuration of the buttons for MANUAL operating status
AUTOMATIC operating state (manual LED is not lit):
Button
Function
LED
1
Press longer than 2 s
(< 5 s)
Activates/deactivates CUTOFF
function
Cutoff LED flashes at 5 Hz
(0 – 2 s) and at 10 Hz (2 – 5 s)
CUTOFF function aktive:
cutoff LED is lit
Press longer than 5 s
Starting the X.TUNE function
Status LED is lit orange
2
Press longer than 2 s
Activates/deactivates CHARACT
function
Charact LED flashes at 5 Hz
(0 – 2 s) and at 10 Hz (2 – 5 s)
CHARACT function aktive:
charact LED is lit
1 and 2
simultane-
ously
Press longer than 2 s
(< 10 s)
Switching to MANUAL operating
state
Manual LED flashes at 5 Hz
(0 – 2 s)
Operating state MANUAL
aktive: manual LED is lit
Press longer than 10 s
(< 30 s)
Device restart
Manual LED, charact LED
and cutoff LED flash at 5 Hz
(10 – 30 s)
Press longer than 30 s
Reset device to factory setting
Manual LED, charact LED
and cutoff LED flash at 10 Hz
(> 30 s)
Table 9:
Configuration of the buttons for AUTOMATIC operating status
15) Depending on the operating principle of the actuator.
english
Type 8696, REV.2
Summary of Contents for 8696
Page 74: ...74 english Type 8696 REV 2...
Page 75: ...www burkert com...