25
Technical data
6.10
Factory settings of the positioner
Functions can be activated via buttons:
Function
Parameter
Value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Characteristic correction
FREE
11)
Table 6:
Factory settings
Functions can be activated via communications software:
Function
Parameter
Value
INPUT
6)
Set-point value input
4 – 20 mA, 4-wire
DIR.CMD
Reversal of the effective direction set-
point value
Off
DIR.ACT
Reversal of the effective direction of
the actuator
Off
SPLTRNG
Function deactivated
Signal split range below
Signal split range above
0 %
100 %
X.LIMIT
Function deactivated
Stroke limit below
Stroke limit above
0 %
100 %
X.TIME
Function deactivated
Actuating time Open
Actuating time Closed
(1 s) values determined by
X.TUNE
(1 s) values determined by
X.TUNE
After implementation of
RESET
: 1 s
X.CONTROL
Deadband
Open amplification factor
Close amplification factor
2.0 %
(1) values determined by
X.TUNE
(1) values determined by
X.TUNE
After implementation of
RESET
: 1
SAFEPOS
Safety position
0 %
SIG.ERROR
12)
Function deactivated
Cable break detection set-point value
Deactivated
BINARY.IN
12)
Digital input function
Operating principle of digital input
Safety position
Normally open
OUTPUT
12)
(variant)
Norm signal output: Parameter
Norm signal output: Type
Position (POS)
4 – 20 mA
Table 7:
Factory settings
11) Without change to the settings via the communications software a linear characteristic is stored.
12)
Only for variant without fieldbus communication
english
Type 8696, REV.2