7.3.2.1 Check programmes
Check
pro-
gramme
Description
P 00
Check programme: Purging:
The heating circuit and the domestic hot water circuit are purged via the automatic air sepa-
rator. The heating pump is cyclically actuated. See automatic purge programme for the oper-
ating sequence.
Stored time periods for automatic purging:
Domestic hot water circuit
390 seconds
; heating circuit
390 seconds
.
P 01
Check programme: Full load:
The unit is operated at maximum heat load on successful ignition.
If the max. Volume flow cannot be achieved, the output is limited.
P 02
Check programme: Minimum load:
The unit is operated with a minimal heat load (ignition gas volume) on successful ignition. If
the min. volume flow cannot be achieved, the burner is not started. (Check S.85)
Automatic purge
programme
Automatic check programme:
Start condition and boiler purging:
If the unit/system pressure has fallen below
0.3 bar
for at least
15 seconds
, the point for a
purging sequence is set. The unit/installation purging is started from
0.5 bar
.
If the heating pressure in the primary circuit rises above
0.5 bar
for
30 seconds
(start-up), an
automatic purging function starts. The function starts repeatedly if the system pressure has
fallen below
0.3 bar
for at least
15 seconds
(e.g. purging of heating surfaces or other
causes) during servicing (maintenance). After filling the installation, the purging starts if
0.5 bar
has been exceeded for at least
30 seconds
.
─ The function cannot be stopped, even by the competent person.
─ The burner does not start before the purging process has been completed.
─ After the purging, no air remains in the unit, which reduces the risk of damage caused by
cavitation and of noises in the heating installation.
─ Stored time periods for automatic purging: Domestic hot water circuit
390 seconds
; heat-
ing circuit
390 seconds
.
Following the automatic purging, the volume flow is measured (heating circuit or hot-water
charging circuit) to ensure that the unit has been purged. Purging is completed when the
threshold of the low volume flow (Lower Flow Rate) has been exceeded.
If the threshold has not been exceeded, the purging function was not fulfilled and fault
F.75
is
displayed.
The check programmes are used during start-up and maintenance
in order to operate the unit in a defined condition.
Summary of Contents for Thema Condens AS 48-A
Page 1: ...DEM RD K M MAKS CONDENSE 48 65...
Page 2: ......
Page 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Page 6: ......
Page 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Page 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Page 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Page 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Page 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Page 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Page 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Page 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Page 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Page 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Page 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...