Installing the boiler
7
Logano GB125 oil condensing boiler - Technical specifications are subject to change without prior notice.
29
7.4
Condensate drain
Ensure by means of a correct condensate drain that no
condensate can drain into the boiler.
B
Connect the boiler by means of an acid-resistant
condensate hose with the neutralising system (ac-
cessory).*
B
Routing with a slope of at least 3°.
USER INFORMATION
B
Drain the condensate that is generated
in the flue correctly.
B
Ensure that the condensate drain ter-
minates in a tundish with siphon.
B
When draining the condensate into a
public sewer ensure that country-speci-
fic standards and directives are obser-
ved.
B
Also observe all regional regulations.
Fig. 21
Condensate drain with neutralising system
1
Neutralising system (accessory)
2
Acid-resistant condensate hose
3
Siphon
1
2
3
USER INFORMATION
Ensure that the condensate hose is not
kinked to prevent condensate backing up.
USER INFORMATION
Observe the installation instructions of the
neutralising system.
USER INFORMATION
In accordance with the ATV Code of
Practice A251, neutralising is not required
for low-sulphur fuel oil EL (sulphur content
< 50 ppm) up to 200 kW boiler output.