2
Product description
Logano GB125 BE US/CA - Subject to technical modifications.
10
2.9.2
Conditions for the boiler room and the environment
2.9.3
Fuel conditions
2.9.4
Power supply conditions
2.9.5
Conditions for hydraulic system and water quality
Operating conditions
Notes – Requirement in greater detail
Temperature in the boiler room
40 to 104 °F
(5 to 40 °C)
Relative humidity
max. 90 %
No condensation or precipitation inside the boiler room
Dust/airborne particles
−
Excessive dust inside the boiler room must be avoided when the boiler is operat-
ing, e.g.:
•
Dust from building work
Combustion air supplied from outside must not be excessively loaded with dust
or airborne seed; if necessary, air filters should be installed to prevent this:
•
Air supply contaminated with dust from dirt roads and paths.
•
Air supply contaminated with dust from production and processing facilities, e.g. quar-
ries, mines, etc.
•
Airborne particles from thistles and similar
Halogenated-hydrocarbon com-
pounds
−
The combustion air must be free from halogen-hydrocarbon compounds.
•
Identify the source of halogen-hydrocarbon compounds and seal it off. Where this is
impossible, route combustion air from areas that are not contaminated by halogen-
hydrocarbon compounds.
Small animals
−
Prevent small animals from entering the boiler room, particularly through the air inlet vents –
by installing screens.
Fire safety
−
Maintain clearances between the boiler and flammable materials in accordance with local
regulations. A minimum clearance of 16” is required. Never store flammable materials or liq-
uids in the vicinity of the boiler.
Flooding
−
In case of an acute risk of flooding, disconnect the boiler in time from its fuel and power
supply before water enters the room. Any general and burner components or control equip-
ment that comes into contact with water must be replaced before starting up again.
Tab. 5
Boiler room and ambient conditions
Country
All countries
Fuels
#2 Fuel oil ASTM D396-05 Type 2
Approved for B5 Fuel Oil (5% biodiesel (B100) according ASTM D6751)
Remarks
The burner may only be operated with the specified fuel. Clean and service once a year. Check that the entire
system functions properly at the same time. Immediately remedy faults.
Tab. 6
Country-specific fuels and remarks
Operating conditions
Notes – Requirement in greater detail
Line voltage
110 – 120 V
The outer casing/boiler must be grounded to protect people and in order to function correctly.
Circuit breaker
10 A
Frequency 60 Hz
Protection class
−
IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø (> 1 mm Ø ), no
waterproofing)
Tab. 7
Power supply
Operating conditions
Notes – Requirement in greater detail
Operating pressure (above atmo-
spheric)
15 – 44 psi
(1 to 3 bar)
Maximum 30 psi with the supplied safety valve.
Permissible test pressure
45 – 58 psi
(3 to 4 bar)
Safety temperature limitation by TR
temperature controller
122 – 194 °F
(50 to 90 °C)
Safety temperature limitation by man-
ual reset high limit (STB)
212 °F
(100 °C)
Water quality
−
The heating system may only be filled and topped up with water of domestic water qual-
ity. We recommend a pH level of 8.2 – 9.5.
Tab. 8
Hydraulics and water quality