Heating system inspection
Logano GB125 BE US/CA - Subject to technical modifications.
43
Cleaning the trap
Fig. 46 Siphon versions
B
Remove cap [1] and gasket [2].
B
Lift out float body [3].
B
Remove bottom cap [7] with gasket [6]
(Version A)
B
Clean sealing cone [4] and float body [3].
B
Clean float seat [5].
B
Clean the float body compartment.
B
Remove condensate residues and flush.
B
Reinstall the bottom cap [7] with gasket [6]
(Version A)
B
Screw siphon (Fig. 46, [1]) onto connector of
condensate pan (Fig. 46, [2].
B
Reattach the condensate hoses.
B
Fill with water via the open connector on the siphon.
B
Insert float body [3] and reinstall cap [1] with gasket
[2]. Ensure that the float moves freely in the float body.
Fig. 47 Overview of siphon versions
Two different versions of the siphon are used
on floor standing oil condensing boilers
(Fig. 48 [1]).