6
Positioning the boiler
Logano G315 – 6 720 817 939 (2017/02)
11
6
Positioning the boiler
This chapter describes how to properly position the Logano G315.
6.1
Tools and auxiliary materials
The following tools and auxiliary materials are required for the boiler
assembly (the listed items must be provided by the installer):
• Boiler assembly tool 2.3 (
• Installation kit (accessory)
• Steel hammer and wooden or rubber mallet
• Half-round bastard file
• Screwdriver (Philips and flat head)
• Flat chisel
• Metric wrenches
• Support wedge, flat iron
• Cleaning rags and cloth
• Fine emery cloth
• Wire brush
• 3-in-1 oil
• Solvent (gasoline, mineral spirits)
• Spirit level, tape measure, chalk, straight edge
• Blanking flange with vent facility (for pressure test)
6.1.1
Boiler assembly tool size 2.3
Fig. 4
Boiler assembly tool size 2.3
[1]
Mating flange
[2]
Additional flange
[3]
Compression unit (pressure flange with clamping nut)
[4]
Tie rod
[5]
Extension
[6]
Wedge (size 2.3)
L
1
121-1/4 inches (3080 mm)
L
2
31-1/2 inches (800 mm)
6.2
Recommended wall clearances
Fig. 5
Installation room with boiler
Observe the recommended wall clearances for complete opening of the
burner door, for boiler installation and for cleaning and maintenance
Fig. 5.
The burner door can be hung with the hinges on the right or left.
When installing your boiler maintain the recommended minimum
dimensions. Select the recommended clearances between wall and
boiler for easy access for installation, maintenance and service work.
The wall clearance on the hinge side must be at least the burner
projection (AB). A distance of AB +4 inches (AB + 100 mm) from the
wall is recommended.
The length LK depends on the number of boiler sections or boiler rating
NOTICE:
Risk of damage from freezing.
▶ Install the system in a room free from thedanger of
freezing.
6 720 642 623-03.1o
3
2
1
6
4
5
L
1
L
2
L
2
Boiler sections
Assembly
tool(s) per
boiler hub
Extension piece
per boiler hub
Length (total) in
inches (mm)
5...9
1
3
121-1/4
(3080 mm)
Table 7
For the correct arrangement of the flange when
performing the assembly procedure, refer to page 22.
6 720 642 621-02.1o
L
K
(400 mm)
≥ 15 3/4"
(880 mm)
34 41/64"
(AB+100 mm)
AB + 4"
AB
A
(~ 750 mm)
29 1/2"
Summary of Contents for Logano G315
Page 55: ...Appendix Logano G315 6 720 817 939 2017 02 55 ...
Page 56: ......