Correcting faults and troubleshooting
11
Logamatic 4321/4322 - Technical specifications are subject to change without prior notice.
73
11.2 Troubleshooting
Fault
Effect
Remedy
Burner fault
Heating remains cold.
–
Service burner as described in the boiler or burner
documentation.
Boiler remains cold
Heating remains cold in
some cases but not always.
–
Check that the temperature control is set to
AUT
.
–
Check that sufficient fuel is available.
If not successful:
–
Set burner emergency switch on control to manual
mode.
–
Set the burner manual switch on the ZM432 module
to
max/I+II
, and set the boiler water temperature
using the thermostat.
–
Notify heating contractor.
DHW temperature does
not rise
DHW remains cold in some
cases but not always.
–
Check that the temperature control is set to
AUT
.
If not successful:
–
Set DHW and heating zone manual switch on the
FM441 module to manual mode.
–
Notify heating contractor.
Safety chain has tripped
Heating remains cold.
–
Check that the boiler is completely full of water.
Check whether the boiler is under at least 14.5 psi
(1.0 bar) pressure.
If this is the case:
–
Unlock the safety temperature switch by unscrewing
the cap nut and pressing the reset button under it.
If not successful:
–
Notify heating contractor.
Remote control fault
The control operates with
the last values set at the
remote control.
–
Notify heating contractor.
Boiler sensor fault;
Outdoor temperature
sensor fault;
Flow sensor fault
The heater heats at higher
temperatures if necessary
and in order to ensure a
comfortable temperature.
–
Notify heating contractor.
Inform the heating contractor which temperature
sensor is defective.
DHW sensor fault
If the DHW sensor is
defective, water is not
heated for safety reasons.
–
Notify heating contractor.
Heating zone X
in manual mode;
DHW in manual mode;
Boiler loop in manual
mode;
Burner in manual mode
Pumps, actuators etc. are
manually switched
depending in the switch
positions.
The control functions
continue operating during
manual mode but do not
affect the system.
–
The switches are set to manual mode (for servicing
or to correct errors).
Return the manual switches to
AUT
when faults
have been remedied.
Tab. 4
Troubleshooting