Page 13
MINIMUM CLEARANCES
The New Buck Corporation Model 20 must be installed in compliance with instructions contained in this manual.
CLEARANCE FROM COMBUSTIBLE WALLS AND CEILINGS (Using single wall chimney connector)
The minimum lateral distance between any part of the room heater and combustible walls is shown in Figures 1
and 2.
FIGURE 1 WALL INSTALLATION FIGURE 2 CORNER INSTALLATION
FLOOR PROTECTION
If a freestanding model is to be installed on a combustible floor, a non-combustible pad must be placed below it to
protect floor from burning material from stove. UL tests were conducted without a floor protector. Therefore,
protector can be of any thickness and any K* factor.
The unit must be positioned on pad so that there is a minimum of 16” from the front of door opening to front of
pad and a minimum of 8” measured horizontally from the sides of fuel loading and ash removal openings to sides
of pad.
NOTE: For clearance reductions using wall protectors, refer to the NFPA -211 code.