6
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
50CY502286 2.0
CAUTION - NOTICE TO RIGGERS
PRUDENCE - AVIS AUX MANIPULATEUR
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
DUCTS
DETAIL A
VOIR DÉTAIL A
MINIMUM HEIGHT: 36" (914.4 mm)
HAUTEUR MINIMUM
UNIT HEIGHT
HAUTEUR D'UNITÉ
SEE DETAIL A
VOIR DÉTAIL A
BANDE SCELLANT DOIT ÊTRE
EN PLACE AVANT DE PLACER
L'UNITÉ SUR LA BASE DE TOIT
A09051
RIGGING WEIGHTS (SMALL CABINET)
RIGGING WEIGHTS (LARGE CABINET)
Unit
24
30
Unit
36*
42*
48*
60*
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
Rigging
Weight
354
161
346
157
Rigging
Weight
426
193
472
214
460
209
506
230
* For 460 volt units, add 14 lb (6.4 kg) to the weight.
NOTE: See dimensional drawing for corner weight distribution.
Fig. 5 -- Rigging Weights
Step 4 — Rig and Place Unit
Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated
structures, etc.).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles,
clevis pins, and straps should be visually inspected for any damage,
evidence of wear, structural deformation, or cracks. Particular
attention should be paid to excessive wear at hoist hooking points
and load support areas. Materials showing any kind of wear in
these areas must not be used and should be discarded.
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
injury or death.
Never stand beneath rigged units or lift over people.
!
WARNING
1. Leave top shipping skid on the unit for use as a spreader bar
to prevent the rigging straps from damaging the unit. If the
skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury.
When straps are taut, the clevis should be a minimum of 36
in. (914 mm) above the unit top cover.
!
WARNING
Rigging/Lifting of Unit (See Fig. 5)
Lifting holes are provided in base rails as shown.
1. Attach shackles, clevis pins, and straps to the base rails of
the unit. Be sure materials are rated to hold the weight of the
unit (See Fig. 5).
2. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
After the unit is placed on the roof curb or mounting pad, remove
the top skid.
607C
--
--
A
Summary of Contents for PREFERRED 607C--A Series
Page 3: ...3 A09426 Fig 2 607 A24 30 Unit Dimensions 607C A ...
Page 4: ...4 A09427 Fig 3 607 A36 60 Unit Dimensions 607C A ...
Page 11: ...11 A10197 Fig 12 Connection Wiring Schematics 208 230 1 60 607C A ...
Page 12: ...12 A10197 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 607C A ...
Page 13: ...13 A10194 Fig 13 Connection Wiring Schematics 208 230 3 60 607C A ...
Page 14: ...14 A10194 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 607C A ...
Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 607C A ...
Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 607C A ...
Page 41: ...41 A10059 Fig 45 Economizer Wiring Diagram 607C A ...
Page 43: ...43 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 607C A ...
Page 44: ...44 A10199 Fig 47 Connection Wiring Diagram 460 3 607C A ...
Page 45: ...45 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 607C A ...