9
Single phase units:
1. Run the high--voltage (L1, L2) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L2 to yellow wire on connection 23 of
the compressor contactor.
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
EQUIP GR
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL
)
W1
Y
G
R
C
WHT(W1)
YEL(Y)
GRN(G)
RED(R)
BRN(C)
THERMOSTAT
(TYPICAL)
ORN(O)
3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS
W2
VIO (W2)
O
SPLICE BOX
DH
BLU(DH)
3-Phase
Only
GRA(Y2)
A09071
Fig. 9 -- High-- and Control--Voltage Connections
Three--phase units:
1. Run the high--voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L3 to yellow wire on connection 13 of
the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
Special Procedures for 208--V Operation
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system and install lockout tag. With disconnect
switch open, move black wire from transformer (3/16 in.)
terminal marked 230 to terminal marked 208. This retaps
transformer to primary voltage of 208 vac.
!
WARNING
Control Voltage Connections
NOTE
: Do not use any type of power--stealing thermostat. Unit
control problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35
°
C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the
control voltage wires), use no. 16 AWG color--coded, insulated
(35
°
C minimum) wires.
Standard Connections
Locate the eight (nine on 3--phase) low voltage thermostat leads in
24 volt splice box. See Fig. 9 for connection diagram. Run the
low--voltage leads from the thermostat, through the control wiring
inlet hole grommet (Fig. 2 and 3), and into the low--voltage splice
box. Provide a drip loop before running wires through panel.
Secure and strain relief all wires so that they do not interfere with
operation of unit. A gray wire is standard on 3--phase units for
connection to an economizer.
If an accessory electric heater is installed, low voltage leads from
heater must be connected to factory supplied control leads from
Indoor Fan Board P4 connector. Factory wires are provided for
electric heat staging W1 and W2 (W2 and W3 on IFB). If room
thermostat has only one stage of supplemental heat, connect white
and violet wires shown in Fig. 9 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire).
Consult unit wiring diagram and electric heater wiring diagram for
additional details.
Transformer Protection
The transformer is of the energy--limiting type. It is set to withstand
a 30--second overload or shorted secondary condition. If an
overload or short is present, correct overload condition and check
for blown fuse on Interface Fan Board. Replace fuse as required
with correct size and rating.
Accessory Electric Heaters Installation
Electric heaters may be installed with the 607----A units per
instructions supplied with electric heater package. See unit rating
plate for factory--approved electric heater kits.
Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the
blower motor for continuous fan.
b. COOLING MODE
(1.) If indoor temperature is above temperature set
point, thermostat closes circuits R to G, R to Y and
R to O--The unit delivers cooling airflow.
c. ELECTRIC HEATING MODE
(1.) Thermostat closes circuit R to W/W1, or W2 and R
to G. There are no on or off delays.
d. HEAT PUMP HEATING MODE
(1.) Thermostat closes circuits R to G and R to Y. The
compressor, indoor and outdoor fans are energized.
e. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
(1.) Thermostat closes circuits R to G, R to Y and R to
W/W1 or W2. The compressor, indoor and outdoor
fans are energized, as well as the electric heat
relays.
f. DEFROST MODE
The defrost mode is automatically energized by the
defrost board during heating mode. The defrost board
energizes “O” (reversing valve) and “W2” (electric
heat). It also de--energizes the outdoor fan. When defrost
is complete, unit will return to heating mode. If room
thermostat is satisfied during defrost, unit will shut
down and restart in defrost on next call for heat.
607C
--
--
A
Summary of Contents for PREFERRED 607C--A Series
Page 3: ...3 A09426 Fig 2 607 A24 30 Unit Dimensions 607C A ...
Page 4: ...4 A09427 Fig 3 607 A36 60 Unit Dimensions 607C A ...
Page 11: ...11 A10197 Fig 12 Connection Wiring Schematics 208 230 1 60 607C A ...
Page 12: ...12 A10197 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 607C A ...
Page 13: ...13 A10194 Fig 13 Connection Wiring Schematics 208 230 3 60 607C A ...
Page 14: ...14 A10194 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 607C A ...
Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 607C A ...
Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 607C A ...
Page 41: ...41 A10059 Fig 45 Economizer Wiring Diagram 607C A ...
Page 43: ...43 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 607C A ...
Page 44: ...44 A10199 Fig 47 Connection Wiring Diagram 460 3 607C A ...
Page 45: ...45 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 607C A ...