Step 3 — Outdoor Fan
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit. Damage to unit may result.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off
motor shaft.
5. When replacing fan blade, position blade back to same posi-
tion as before.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.
Step 4 — Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panels (see Fig 22) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any discolored or burned
connections are noticed, disassemble the connection, clean all the
parts, restrip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each
electrical
component
with
the
proper
electrical
instrumentation. Refer to the unit wiring label when making these
checkouts.
Step 5 — Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a
refrigerant leak.
If oil is detected or if low performance is suspected, leak--test all
refrigerant tubing using an electronic leak detector, or liquid--soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
Step 6 — Indoor Airflow
The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem exists, be
sure that all supply--air and return--air grilles are open and free
from obstructions, and that the air filter is clean. When necessary,
refer to Indoor Airflow and Airflow Adjustments section to check
the system airflow.
Step 7 — Metering Devices--TXV & Piston
This unit uses 2 types of metering devices. The outdoor metering
device is a fixed orifice and is contained in the brass hex--body in
each liquid line feeding the outdoor coils. The indoor metering
device is a TXV type device.
607C
--
--
A
Summary of Contents for PREFERRED 607C--A Series
Page 3: ...3 A09426 Fig 2 607 A24 30 Unit Dimensions 607C A ...
Page 4: ...4 A09427 Fig 3 607 A36 60 Unit Dimensions 607C A ...
Page 11: ...11 A10197 Fig 12 Connection Wiring Schematics 208 230 1 60 607C A ...
Page 12: ...12 A10197 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 607C A ...
Page 13: ...13 A10194 Fig 13 Connection Wiring Schematics 208 230 3 60 607C A ...
Page 14: ...14 A10194 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 607C A ...
Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 607C A ...
Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 607C A ...
Page 41: ...41 A10059 Fig 45 Economizer Wiring Diagram 607C A ...
Page 43: ...43 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 607C A ...
Page 44: ...44 A10199 Fig 47 Connection Wiring Diagram 460 3 607C A ...
Page 45: ...45 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 607C A ...