36
Right Hood
Side Panel
Hood Top Panel
Left Hood
Side Panel
Hood
Divider
A09700
Fig. 34 -- Hood Assembly
A09701
Fig. 35 -- Economizer Hood Installation
11. Open the filter clips on the inside of the hood top. Insert the
aluminum filter into the hood and close the clips to hold in
place. See Fig. 36.
12. To replace air filters, open filter access door remove old
filters and install new disposable filters in filter rack. See
Table 14 for filter part numbers.
IMPORTANT
: On the the bent coil (See Fig. 37 to determine coil
type) filter rack, the 18 x 24 x 1 (257.2mm x 609.6mm x25.4mm)
filter must be installed through the filter access door first then
install the 16 x 24 x 1 (406.4mm x 609.6mm x 25.4mm) filter.
NOTE
:
The economizer control settings and the filters are
accessible through the filter access door.
Table 14 – Filter Part Number
DESCRIPTION
PART NUMBER
Straight Indoor
Coil Air Filter
14 x 24 x 1
(355.6 x 609.6 x 25.4 mm)
KH01AA314
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
KH01AA316
Bent Indoor
Coil Air Filter
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
KH01AA316
18 x 24 x 1
(457.2 x 609.5 x 25.4 mm)
KH01AA318
13. Economizer controls are set to a standard factory setting.
Nevertheless, you can adjust these settings through the filter
access door. Review the settings in the Operation section:
(1.) The standard economizer controller has a factory
setting of “C” for the outdoor air temperature
changeover and 63
_
F (17
_
C) for the supply air
(mixed air) temperature sensor. The outdoor air
temperature changeover setting is adjusted on the
sensor by setting the dip switches on the sensor.
The ABCD potentiometer on the economizer
control should be set to the “D” position.
(2.) The low ambient compressor lockout switch setting
is fixed at 42
_
F (5.6
_
C).
(3.) The minimum position for the outdoor air damper
can be configured at the controller. When not using
a CO
2
sensor, the DCV Max potentiometer must be
completely closed (CCS) for the Minimum Posi-
tion potentiometer to function correctly.
(4.) Settings for the optional outdoor enthalpy sensor,
indoor enthalpy sensor, and CO
2
sensor can also be
configured at the controller.
14. Replace the filter access panel. Screw in place ensuring all
seams are air and watertight.
15. Install all economizer accessories then power HVAC unit
and test cycle economizer.
607C
--
--
A
Summary of Contents for PREFERRED 607C--A Series
Page 3: ...3 A09426 Fig 2 607 A24 30 Unit Dimensions 607C A ...
Page 4: ...4 A09427 Fig 3 607 A36 60 Unit Dimensions 607C A ...
Page 11: ...11 A10197 Fig 12 Connection Wiring Schematics 208 230 1 60 607C A ...
Page 12: ...12 A10197 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 607C A ...
Page 13: ...13 A10194 Fig 13 Connection Wiring Schematics 208 230 3 60 607C A ...
Page 14: ...14 A10194 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 607C A ...
Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 607C A ...
Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 607C A ...
Page 41: ...41 A10059 Fig 45 Economizer Wiring Diagram 607C A ...
Page 43: ...43 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 607C A ...
Page 44: ...44 A10199 Fig 47 Connection Wiring Diagram 460 3 607C A ...
Page 45: ...45 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 607C A ...