background image

4. Remove thermostat cover and place base against wall in a

near level position. Fasten to wall by driving 2 of the screws
provided with thermostat through slots in center of base and
into wall. (See Fig. 22.)

5. Remove and discard foam shipping pad from inside ther-

mostat.

CAUTION:

Failure to remove foam shipping pad will

damage thermostat.

6. Level thermostat with a level. (See Fig. 23.) Tighten 2

mounting screws then drive 2 remaining screws through
holes in upper corners of base and into wall. (See Fig. 23.)

NOTE:

Thermostat must be level for proper unit operation.

7. Set thermostat heat anticipator to appropriate value based

on the heater size for unit being installed. (See Fig. 24 and
Table 7.)

8. Replace thermostat cover by hooking tabs on top lip of

cover into slots in top retaining post and swinging cover
down until it snaps over lower retaining post.

9. Set outdoor thermostat to 50°F.

NOTE:

Refer to Installation Instructions packaged with thermo-

stat for additional information.

ELECTRONIC HEAT PUMP THERMOSTATS
(PROGRAMMABLE AND NON-PROGRAMMABLE)

1. Install Outdoor Temperature Sensor. Follow Installation

Instructions included with sensor and route wires through
hole in wall along with thermostat cable.

2. Open thermostat rear door (mounting base) to expose

mounting holes. The base can be removed to simplify
mounting. Snap apart carefully at hinge to separate mount-
ing base from remainder of thermostat.

3. Route thermostat wires through large hole in mounting

base.

4. Level mounting base against wall and mark wall through 2

mounting holes.

5. Drill two 3/16-in. mounting holes in wall where marked.

6. Secure mounting base to wall with 2 screws and anchors

provided, making sure all wires extend through mounting
base.

7. Adjust wire length and routing to allow proper closure of

thermostat. Strip each wire end no more than 1/4-in. to
prevent adjacent wires from shorting together. Match and
connect equipment lead wire to correct terminals of the
thermostat connector. (See Fig. 25 and 26.)

NOTE:

All TSTAT models have no batteries and are not "power

stealing." They do require 24 vac (R and C terminals) to be
connected for proper operation. Thermostat will not operate
without these 2 connections.

8. Push excess wiring into wall. Seal hole in wall to prevent

drafts.

9. Snap hinge back together.

10. Turn on power to unit.

11. Reconfigure thermostat to allow thermostat and outdoor

temperature sensor to control electric heat lockout.

This configuration allows lockout of any W (Electric Heat)
when outdoor temperature is above a selected value. Tem-
peratures of 15° to 55°F (or equivalent values in °C) can be
selected. Feature can be enabled or disabled. EMER-
GENCY HEAT mode disables this feature. Factory default
is OFF (disabled.)

To enable feature and set temperature value proceed as
follows:

a. Non-Programmable Model

(1.) Enter thermostat configuration mode by pressing

and holding FAN button for approximately 10 sec.
The room temperature disappears and display
should read "1-." Thermostat is now in configura-
tion mode.

Fig. 22—Thermostat Mounting Screw Location

A95373

MOUNTING HOLE

MOUNTING HOLE

Fig. 23—Leveling Thermostat

A95356

80
70
60

50

80

70

60

50

ON

AUTO

FAN

COOL

OFF

HEAT

EM HEAT

TABLE 7—HEAT ANTICIPATOR VALUES FOR

HEAT PUMP UNITS

HEATER SIZE (KW)

ANTICIPATOR SETTING

0

N/A

5

0.35

10

0.35

15

0.70

20

0.70

N/A—Not Applicable

Fig. 24—Setting Heat Anticipator

A95357

COOL

COOL

HEAT

EM HEAT

LONGER

1.2 .8.6 .4

.2

.3

.15

.12

.10

   HEAT ANTICIPATOR INDICATOR

—11—

Summary of Contents for MA1A

Page 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Page 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Page 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Page 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Page 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Page 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Page 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Page 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Page 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Page 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Page 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Page 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Page 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Page 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Page 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Page 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Reviews: