NOTE: If FAN button is pressed again or if no
button is pressed for 60 sec, thermostat will exit
configuration mode and return to normal operation.
To re-enter configuration mode, the FAN button
must be pressed and held for 10 sec again.
(2.) Use up and down buttons until thermostat display
reads "6-."
(3.) Press MODE button once to display current selec-
tion of OF, 15, 20, 25, 30, 35, 40, 45, 50, or 55.
Value should be OF for feature disabled.
(4.) Use up and down buttons to change from OF to 1 of
the available temperature choices. Value will de-
pend on ambient temperature at which heat pump
can no longer handle heating load.
(5.) Press FAN button to exit configuration mode.
b. Programmable Model
(1.) Enter thermostat configuration mode by pressing
and holding FAN button for approximately 10 sec.
The room temperature disappears and display
should read "--." Thermostat is now in configura-
tion mode.
NOTE: If no button is pressed for 10 sec, thermo-
stat will exit configuration mode and resume normal
operation. To re-enter configuration mode, FAN
button must be pressed and held for 10 sec again.
(2.) Press COPY PREVIOUS DAY button to display
current selection of OF, 15, 20, 25, 30, 35, 40, 45,
50, or 55. Value should be OF for feature disabled.
(3.) Use the up and down buttons to change from OF to
1 of the available temperature choices. Value will
depend on ambient temperature at which heat pump
can no longer handle heating load.
(4.) Wait 10 sec to exit configuration mode.
12. Jumper terminals W2 and E on unit terminal strip. This
allows electric heat to be activated when EMERGENCY
HEAT option is selected at thermostat.
13. With an electronic thermostat such as this one, it should not
be necessary to change the factory default heat anticipation
setting. Consult thermostat Installation Instructions if heat
anticipation must be adjusted.
NOTE:
Refer to Installation Instructions packaged with thermo-
stat for additional information.
D.
Make Low-Voltage Connections at Unit
Attach thermostat wires to low-voltage terminal block on left side
of control box in locations indicated on label adjacent to terminal
block or appropriate thermostat wiring diagram in these instruc-
tions.
NOTE:
Any unused conductors of thermostat cable not required
should be left unattached.
CAUTION:
Recheck wiring color code schedule to be
certain proper terminals are connected before applying
power. Improper wiring or installation may damage
thermostat.
Fig. 25—Heat Pump Circuit Connections
(Non-Programmable Electronic Thermostat)
NOTE:
Terminals O/W2, Y1, and L are not used on thermostat. An
outdoor temperature sensor must be connected to thermostat terminals
S1 and S2. X terminal on control voltage terminal strip must be
connected to C terminal on thermostat for proper thermostat opera-
tion. Terminals W2 and E must be jumpered on unit terminal block.
A95415
24 VAC HOT
24 VAC COMM
HEAT STAGE 2
COOL/ HEAT
STAGE 1
FAN
R
C
G
W/W1
Y/Y2
R
X
RVS COOLING
N/A
RVS HEATING
OUTDOOR
SENSOR
CONNECTION
Y1
B
S1
S2
OUTDOOR
TEMPERATURE
SENSOR
CONTROL
VOLTAGE
TERMINAL
STRIP
Y
G
O/W2
L
B
E
TROUBLE OR
CLEAN FILTER
W2
MODEL HP
NON-PROGRAMMABLE
ELECTRONIC
THERMOSTAT
Fig. 26—Heat Pump Circuit Connections
(Programmable Electronic Thermostat)
NOTE:
Terminals O/W2, Y1/W2, and L are not used on thermostat.
An outdoor temperature sensor must be connected to thermostat
terminals S1 and S2. X terminal on control voltage terminal strip must
be connected to C terminal on thermostat for proper thermostat
operation. Terminals W2 and E must be jumpered on unit terminal
block.
A95416
24 VAC HOT
FAN
HEAT STAGE 2
COOL /HEAT
STAGE 1
RVS COOLING
N/A
R
G
W/W1
Y/Y2
O/W2
Y1/W2
R
G
24 VAC COMM.
RVS HEATING
TROUBLE
OUTDOOR
SENSOR
CONNECTION
C
B
L
S1
S2
X
CONTROL
VOLTAGE
TERMINAL
STRIP
OUTDOOR
TEMPERATURE
SENSOR
W2
Y
E
B
MODEL HP
PROGRAMMABLE
ELECTRONIC
THERMOSTAT
—12—