background image

b. Programmable Model

(1.) Enter thermostat configuration mode by pressing

and holding FAN button for approximately 10 sec.
The room temperature disappears and display
should read "--." Thermostat is now in configura-
tion mode.
NOTE: If no button is pressed for 10 sec, thermo-
stat will exit configuration mode and resume normal
operation. To re-enter configuration mode, FAN
button must be pressed and held for 10 sec again.

(2.) Press HOLD button to display current selection of

OF (off) or ON (on). Factory default is OF for off.

(3.) Use the up or down button to change from OF (off)

to ON (on).

(4.) Wait 10 sec to exit configuration mode.

NOTE:

Refer to the electronic thermostat Installation Instructions

for more information if needed.

11. With an electronic thermostat such as this one, it should not

be necessary to change the factory default anticipation
setting. Consult thermostat Installation Instructions if heat
anticipation must be adjusted.

HONEYWELL HEAT PUMP THERMOSTAT

1. Strip approximately 1/2-in. of insulation off end of each

wire routed through hole in wall.

2. Connect thermostat wires to thermostat by placing colored

wire under appropriate terminal screw on back of thermo-
stat as indicated by label over low-voltage terminal block
located on left side of control box. (See Fig. 21.)

3. Push all but approximately 2 in. of thermostat cable back

into wall. Seal opening around cable to prevent drafts
through hole which could interfere with operation of unit.

Fig. 19—Air Conditioning Circuit Connections

(Non-Programmable Electronic Thermostat)

NOTE:

X terminal on control voltage terminal strip must be con-

nected to C terminal on thermostat for proper thermostat operation.

A95413

24 VAC HOT

24 VAC COMM

HEAT STAGE 1

COOL STAGE 1

FAN

R

C

W/W1

R

X

MODEL AC

NON-PROGRAMMABLE

ELECTRONIC

THERMOSTAT

CONTROL

VOLTAGE

TERMINAL

STRIP

W

Y

G

Y/Y2

G

Fig. 20—Air Conditioning Circuit Connections

(Programmable Electronic Thermostat)

NOTE:

Terminals O/W2, Y1/W2, B, and L are not used on thermo-

stat. X terminal on control voltage terminal strip must be connected to
C terminal on thermostat for proper thermostat operation. An optional
outdoor temperature sensor may be connected to S1 and S2 terminals
on thermostat.

A95414

24 VAC HOT

FAN

HEAT STAGE 1

COOL STAGE 1

N/A

N/A

R

G

W/W1

Y/Y2

O/W2

Y1/W2

R

G

W

Y

24 VAC COMM.

N/A

N/A

OUTDOOR

SENSOR

CONNECTION

C

B

L

S1

S2

X

CONTROL

VOLTAGE

TERMINAL

STRIP

MODEL AC

PROGRAMMABLE

ELECTRONIC

THERMOSTAT

Fig. 21—Heat Pump Circuit Connections

(Honeywell Thermostat)

NOTE:

Terminals O, L, and W3 are not used on thermostat.

A95355

THERMOSTAT

CONTROL

VOLTAGE

TERMINAL

STRIP

FAN

24 VAC HOT

COOL/HEAT

STAGE 1

RVS HEATING

EMERGENCY

HEAT

HEAT

STAGE 2

NOT USED

NOT USED

NOT USED

GREEN

RED

YELLOW

BLUE

WHITE

BROWN

G

R

Y

B

G

R

Y

B

W

2

W

3

W

2

E

E

O

X

L

—10—

Summary of Contents for MA1A

Page 1: ...manufactured homes These units are available in the cooling sizes shown in Table 1 The MA1A and MH1A are single package units All components including outdoor coil compressor and refrigerant tubing a...

Page 2: ...e thermostat wire with less than the recommended number of conductors CAUTION Failure to adhere to indoor air outdoor air and exhaust air requirements as listed in the following sections will void uni...

Page 3: ...clearance C Recommended Unit Clearances For serviceability and elimination of compressor vibration trans mission it is recommended that the sides and back of unit be installed with a minimum 1 in clea...

Page 4: ...n See Fig 9 4 Place base template assembly over hole and mark indoor air plenum cutout in supply duct trunk measuring 13 in by 9 1 8 in See Fig 10 Mark condensate drain hose and outdoor air plenum cut...

Page 5: ...nit and base template into floor Tighten screws flush to foam seal Overtightening screws will tip unit forward on foam seal Do NOT use any other procedure to permanently secure unit to structure 4 Cov...

Page 6: ...panel or fuse box Refer to Table 3 and Table 4 for required circuits and recommended wire size for each circuit The unit is equipped with circuit breakers enclosed in wiring compartment This compartme...

Page 7: ...ps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft Amps Ampacity Wire Size Max Fuse Size Amps Max Wire Length Ft 5 018 024 030 036 23 9 29 9 10 30 80 N A N A N A N A N A 10 018 024 030 036 44...

Page 8: ...LE TYPE APPLICATION THERMOSTAT NO OF CONDUCTORS REQUIRED 18 GAGE REQUIRED CONNECTIONS WIRING DIAGRAM Air Conditioner Robertshaw TX400 42K 4 G R Y W Fig 18 TSTATPPNAC01 A 5 R C W W1 Y Y2 G Fig 19 TSTAT...

Page 9: ...s 4 Drill two 3 16 in mounting holes in wall where marked 5 Secure mounting base to wall with 2 screws and anchors provided making sure all wires extend through mounting base 6 Adjust wire length and...

Page 10: ...3 Push all but approximately 2 in of thermostat cable back into wall Seal opening around cable to prevent drafts through hole which could interfere with operation of unit Fig 19 Air Conditioning Circu...

Page 11: ...e to wall with 2 screws and anchors provided making sure all wires extend through mounting base 7 Adjust wire length and routing to allow proper closure of thermostat Strip each wire end no more than...

Page 12: ...be adjusted NOTE Refer to Installation Instructions packaged with thermo stat for additional information D Make Low Voltage Connections at Unit Attach thermostat wires to low voltage terminal block on...

Page 13: ...from skirting or foundation wall to entrance of outdoor air plenum See Fig 27 for a typical air tunnel 2 The condensate drain must not be allowed to drain inside air tunnel Pipe to outside of home See...

Page 14: ...UCTBOARD 2 X 2 TREATED LUMBER Fig 28 Drain Pipe Routing A95384 NET FREE AREA SEE VENTILATION REQUIREMENTS TABLE SIZES MAY VARY AS LONG AS THE MINIMUM NET FREE OPEN AREA INCLUDING GRILLE MEETS THE REQU...

Page 15: ...FSET FLASHING FLASHING ROOFCAP ATTIC AREA ATTIC AREA FLEX DUCT FLEX DUCT NOTE THE FLEX DUCT SHOULD BE A STRAIGHT RUN FROM UNIT TO ROOFCAP TYPICAL FRONT VIEW TYPICAL SIDE VIEW TYPICAL FRONT VIEW TYPICA...

Page 16: ...The compressor should energize and cool air should blow through registers Once cooling test is complete return system control to OFF setting Wait 5 minutes c Set system control to HEAT and raise tempe...

Reviews: