terminal. See Table 13 for lead color identification. Recon-
nect original lead on SPARE terminal.
Follow this same procedure for proper selection of COOL
speed selection.
C.
Adjust Blower Off Delay (Heat Mode)
The blower off delay has 4 adjustable settings from 90 sec to 180
sec. (See Table 14.) The blower off delay jumpers are located on
the furnace control board (See Fig. 31). To change the blower off
delay setting, move the jumper from one set of pins on the control
board to the pins used for the desired blower off delay. Factory
blower off delay setting is 120 sec.
D.
Set Thermostat Heat Anticipator
When using a nonelectronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of the electrical
components in R-W circuit. Accurate amp draw readings can be
obtained at thermostat subbase terminals R and W. Fig. 60
illustrates an easy method of obtaining actual amp draw. The amp
reading should be taken after blower motor has started and furnace
is heating. Connect ammeter wires as shown in Fig. 60. The
thermostat anticipator should NOT be in the circuit while measur-
ing current. If themostat has no subbase, the thermostat must be
disconnected from R and W wires during current measurement.
See thermostat manufacturer’s instructions for adjusting heat
anticipator and for varying heating cycle length. For an electronic
thermostat, set cycle rate for 3 cycles per hour.
V.
CHECK SAFETY CONTROLS
This section covers the safety controls that must be checked before
the installation is complete. The flame sensor, gas valve, and
pressure switch were all checked in the Start-up procedure section
as part of normal operation.
TABLE 10—MODEL 350MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (CONTINUED)
FOR USE WITH 140 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2 PERCENT FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
4001
to
5000
9%
derate
725
41
3.6
41
3.7
41
3.8
40
3.6
40
3.8
750
42
3.7
42
3.8
41
3.6
41
3.7
41
3.8
775
42
3.5
42
3.6
42
3.7
42
3.8
41
3.6
800
42
3.3
42
3.4
42
3.5
42
3.6
42
3.7
825
42
3.7
42
3.2
42
3.3
42
3.4
42
3.5
850
43
3.5
43
3.6
43
3.8
42
3.2
42
3.3
875
43
3.3
43
3.4
43
3.6
43
3.7
43
3.8
900
43
3.1
43
3.3
43
3.4
43
3.5
43
3.6
925
43
3.0
43
3.1
43
3.2
43
3.3
43
3.4
950
43
2.8
43
3.9
43
3.0
43
3.1
43
3.2
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
5001
to
6000
11%
derate
700
41
3.5
41
3.7
41
3.8
40
3.6
40
3.7
725
42
3.7
42
3.8
41
3.5
41
3.6
41
3.8
750
42
3.4
42
3.5
42
3.7
42
3.8
41
3.5
775
42
3.2
42
3.3
42
3.4
42
3.5
42
3.7
800
43
3.7
43
3.8
42
3.2
42
3.3
42
3.4
825
43
3.5
43
3.6
43
3.7
43
3.8
42
3.2
850
43
3.3
43
3.4
43
3.5
43
3.6
43
3.7
875
43
3.1
43
3.2
43
3.3
43
3.4
43
3.5
900
43
2.9
43
3.0
43
3.1
43
3.2
43
3.3
925
43
2.7
43
2.8
43
2.9
43
3.0
43
3.1
950
43
2.6
43
2.7
43
2.8
43
2.9
43
3.0
975
43
2.5
43
2.6
43
2.6
43
2.7
43
2.8
1000
43
2.3
43
2.4
43
2.5
43
2.6
43
2.7
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
Only
6001
to
7000
13%
derate
650
41
3.8
40
3.6
40
3.7
40
3.8
39
3.7
675
41
3.5
41
3.6
41
3.7
40
3.6
40
3.7
700
42
3.6
42
3.7
41
3.5
41
3.6
41
3.7
725
42
3.4
42
3.5
42
3.6
42
3.7
42
3.8
750
43
3.8
42
3.3
42
3.4
42
3.5
42
3.6
775
43
3.6
43
3.7
43
3.8
42
3.3
42
3.4
800
43
3.4
43
3.5
43
3.6
43
3.7
43
3.8
825
43
3.2
43
3.3
43
3.4
43
3.5
43
3.6
850
43
3.0
43
3.1
43
3.2
43
3.3
43
3.4
875
43
2.8
43
2.9
43
3.0
43
3.1
43
3.2
*Orifice numbers 43 are factory installed.
Percents of derate are based on midpoints of U.S. altitude ranges.
—45—