Determine and adjust air temperature rise as follows:
1. Place thermometers in return and supply ducts as close to
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
3. Adjust temperature rise by adjusting blower speed. Increase
blower speed to reduce temperature rise. Decrease blower
speed to increase temperature rise.
WARNING:
Disconnect 115-v electrical power before
changing speed tap. Failure to follow this warning could
result in personal injury.
4. To change blower motor speed selections for heating mode,
remove blower motor lead from control center HEAT
terminal. (See Fig. 31.) Select desired blower motor speed
lead from 1 of the other motor leads and relocate it to HEAT
TABLE 10—MODEL 350MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT
FOR USE WITH 140 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2 PERCENT FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
0
to
2000
0%
derate
850
41
3.6
41
3.7
41
3.8
40
3.6
40
3.8
875
42
3.8
41
3.5
41
3.6
41
3.7
41
3.8
900
42
3.5
42
3.7
42
3.8
41
3.5
41
3.6
925
42
3.4
42
3.5
42
3.6
42
3.7
42
3.8
950
42
3.2
42
3.3
42
3.4
42
3.5
42
3.6
975
43
3.7
43
3.8
42
3.2
42
3.3
42
3.4
1000
43
3.5
43
3.6
43
3.7
42
3.2
42
3.3
1025
43
3.3
43
3.4
43
3.6
43
3.7
43
3.8
1050
43
3.2
43
3.3
43
3.4
43
3.5
43
3.6
1075
44
3.5
44
3.6
43
3.2
43
3.3
43
3.4
1100
44
3.3
44
3.4
44
3.5
43
3.2
43
3.3
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
Altitudes
2001 to
3000
or
Canada
Altitudes
2001 to
4500
5%
derate
775
41
3.7
41
3.8
40
3.6
40
3.7
39
3.6
800
42
3.8
41
3.6
41
3.7
41
3.8
40
3.6
825
42
3.6
42
3.7
41
3.5
41
3.6
41
3.7
850
42
3.4
42
3.5
42
3.6
42
3.7
41
3.5
875
42
3.2
42
3.3
42
3.4
42
3.5
42
3.6
900
43
3.7
43
3.8
42
3.2
42
3.3
42
3.4
925
43
3.5
43
3.6
43
3.7
42
3.2
42
3.3
950
43
3.3
43
3.4
43
3.5
43
3.7
43
3.8
975
43
3.1
43
3.3
43
3.4
43
3.5
43
3.6
1000
43
3.0
43
3.1
43
3.2
43
3.3
43
3.4
1025
43
2.8
43
2.9
43
3.0
43
3.1
43
3.2
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
Only
3001
to
4000
7%
derate
750
41
3.6
41
3.8
40
3.6
40
3.7
40
3.8
775
42
3.8
41
3.5
41
3.6
41
3.7
40
3.6
800
42
3.5
42
3.7
42
3.8
41
3.5
41
3.6
825
42
3.3
42
3.4
42
3.6
42
3.7
42
3.8
850
43
3.8
42
3.2
42
3.4
42
3.5
42
3.6
875
43
3.6
43
3.7
42
3.2
42
3.3
42
3.4
900
43
3.4
43
3.5
43
3.6
43
3.8
42
3.2
925
43
3.2
43
3.3
43
3.5
43
3.6
43
3.7
950
43
3.1
43
3.2
43
3.3
43
3.4
43
3.5
975
43
2.9
43
3.0
43
3.1
43
3.2
43
3.3
1000
43
2.8
43
2.9
43
3.0
43
3.0
43
3.1
* Orifice numbers 43 are factory installed.
Percents of derate are based on midpoints of U.S. altitude ranges.
—44—